1MRS757275
COM600 series, version 4.1
IEC 61850 Proxy Server User's Manual
Property/Parameter
Data Set
Entry ID
Reason Code
Sequence Number
Time Stamp
Trigger Options
Data change
Data Update
Period
Quality Change
Value or value range/Default
True
False
Default: False
True
False
Default: True
True
False
Default: True
True
False
Default: True
True
False
Default: False
True
False
Default: True
True
False
Default: False
True
False
Default: False
True
False
Default: True
Description
Data Set
Entry ID
Reason Code
Sequence Number
Time Stamp
Defines the triggering condi-
tions for creating reports.
Specifies whether a report
entry shall be generated due to
a change of the value of the
data attribute.
Specifies whether a report
entry shall be generated due to
freezing the value of an
unfreezable attribute or updat-
ing the value of any other
attribute. An updated value
may have the same value as
the old value.
Specifies whether a report
entry shall be generated on the
expiration of the integrity
period.
Specifies whether a report
entry shall be generated due to
a change of the value of the
quality attribute.
23