Monitoring Elements - GE UR series Instruction Manual

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
5
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER 1
ARCING CURRENT
5-224

MONITORING ELEMENTS

BREAKER 1
ARCING CURRENT
BREAKER 2
MESSAGE
ARCING CURRENT
BREAKER
MESSAGE
FLASHOVER 1
BREAKER
MESSAGE
FLASHOVER 2
CT FAILURE
MESSAGE
DETECTOR
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
MESSAGE
OPEN POLE
MESSAGE
MONITORING ELEMENTS
BKR 1 ARC AMP
FUNCTION: Disabled
BKR 1 ARC AMP
MESSAGE
SOURCE: SRC 1
BKR 1 ARC AMP INT-A:
MESSAGE
Off
BKR 1 ARC AMP INT-B:
MESSAGE
Off
BKR 1 ARC AMP INT-C:
MESSAGE
Off
BKR 1 ARC AMP
MESSAGE
DELAY:
0.000 s
BKR 1 ARC AMP LIMIT:
MESSAGE
1000 kA2-cyc
BKR 1 ARC AMP BLOCK:
MESSAGE
Off
BKR 1 ARC AMP
MESSAGE
TARGET: Self-reset
BKR 1 ARC AMP
MESSAGE
EVENTS: Disabled
L60 Line Phase Comparison System
5.6.9 MONITORING ELEMENTS
See below.
See below.
See page 5–227.
See page 5–227.
See page 5–231.
See page 5–233.
See page 5–233.
See page 5–234.
BREAKER 1(2) ARCING CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
2
Range: 0 to 50000 kA
-cycle in steps of 1
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS