3.6

Control sequences

3.6.1

Sequences overview (setting via parameter P01)

The mode of the air control sequence can be set via parameter P01.
It is only available with application "Single duct"
In all application the changeover of the air sequence can be done via supply air
temperature sent by the primary controller.
The available sequences depend on the application:
P01 = 0
P01 = 1
Cooling
ü
ü
-
-
1) Changeover air
For the relation between setpoints and sequences, see section 3.6.6.
RDU341 Basic Documentation
P01 = 2
P01 = 3
Manually select
Automatic
heating or
heating /
cooling
cooling
sequence
changeover
ü
-
ü
ü
1)
-
CE1P3172en
2015-06-08
ü
1)
ü
1)
25 / 68