ABB COM600 series User Manual page 21

Snmp opc server
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS757276
COM600 series, Version 4.1
SNMP OPC Server User's Manual
Property/Para-
Value or Value range/ Default
meter
Community Name
public
Write Community
private
Name
Polling
Poll Rate
0 to 3600
Default: 2
Timeout
0 to 3600
default: 5
Security
Authentication
Password
Authentication Pro-
Not Used
tocol
MD5 SHA
Default: Not Used
Encryption
Not Used
Algorithm
DES
AES
3DES
Default: Not Used
Encryption Pass-
word
User name
Control Authoriza-
tion
Description
Community name defined on the network
device. Community name is used to
authenticate SNMP packets, which must
match the community name that is spe-
cified on the agent.
Community name used for the writing
operation. The community name is used
to authenticate SNMP packets, which must
match the community name that is spe-
cified on the agent.
Polling rate in seconds.
A timeout of the component in seconds.
Timeout property is set to 0, all operations
return immediately. If the timeout is set to
a positive value, the system will want for
the operation to complete before returning.
The password used for SNMPv3 authen-
tication.
The authentication protocol used for
SNMPv3.
The encryption algorithm used for
SNMPv3 packets.
The encryption password used for
SNMPv3 privacy.
The user name used for SNMPv3
authentication.
21