STATUS
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.

6.3.10 Digital counters

ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS
 Counter 1
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The

6.3.11 Selector switches

ACTUAL VALUES  STATUS  SELECTOR SWITCHES
 SELECTOR SWITCHES
6
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.

6.3.12 Flex States

ACTUAL VALUES  STATUS  FLEX STATES
 FLEX STATES
There are 256 FlexState

6.3.13 Ethernet

ACTUAL VALUES  STATUS  ETHERNET
 ETHERNET
6-6
Counter 1
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
1970/01/01 00:00:00
Counter 1 MICROS:
0
value refers to the microsecond portion of the time stamp.
COUNTER 1 MICROS
SELECTOR SWITCH 1
POSITION: 0/7
SELECTOR SWITCH 2
POSITION: 0/7
PARAM 1: Off
Off
PARAM 256: Off
Off
TM
bits available. The second line value indicates the state of the given FlexState bit.
ETHERNET PRI LINK
STATUS: Fail
ETHERNET SEC LINK
STATUS: Fail
ACCUM:
Range: YYYY/MM/DD HH:MM:SS
Range: 0 to 4294967295 in steps of 1
Range: Current Position / 7
Range: Current Position / 7
Range: On, Off
Range: On, Off
Range: Fail, OK
Range: Fail, OK
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL