Test Run; Test Run Using Outdoor Unit (Pcb); Test Run Using Remote Controller; Check List (Example) - Fujitsu UTP-VX60A Installation Manual

Airstage
Hide thumbs Also See for UTP-VX60A:
Table of Contents

Advertisement

9. TEST RUN

The test run function will force the outdoor unit to operate. When performing the test run,
confi rm that the entire system including the external devices operates normally. (If only the
outdoor unit operates, it may cause damage to the entire refrigerant system.)

9.1. Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.

9.2. Test run using remote controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller. (If using analog inputs, Fujitsu general remote controller operation
will be disabled.)

10. CHECK LIST (Example)

Pay special attention to the check items below when installing the entire system. After
installation is complete, be sure to check the following check items again.
Check items
Are the external devices and DX-Kit
operating as expected?
Has the indoor unit been installed cor-
rectly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been com-
pleted?
Does water drain easily from the indoor
units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specifi ed
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner op-
eration by remote controller or external
device?
After installation is completed, has the
proper operation and handling been
explained to the user?

11. ERROR CODES

• When an error occurs, the LED on the PC board (LED name: LED1) fl ashes.
• "Error code" can be viewed by connecting the optional wired remote controller, group
remote controller, and IR receiver unit, etc.
If you use a wired type remote controller (Optional parts), error codes will appear on
the remote controller display. If you use a wireless remote controller (IR receiver unit
of optional parts), the lamp on the photodetector unit will output error codes by way of
blinking patterns. See the lamp blinking patterns and error codes in the table below.
Error indications
OPERATION
TIMER lamp
lamp (green)
(orange)
(1)
(2)
(1)
(4)
(1)
(6)
(2)
(6)
En-17
If not performed correctly
No operation, heat or burn damage
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
Short circuit
No operation, heat or burn damage
No cooling, No heating
No operation
Wired Remote
Controller Error
Error contents
FILTER
code
lamp (red)
Remote controller
communication error
Network communication
error
Peripheral unit
communication error
Indoor unit address
setting error
Error indications
OPERATION
TIMER lamp
lamp (green)
(2)
(3)
(3)
(3)
(4)
(4)
Check
box
(5)
(5)
(9)
(13)
(13)
Display mode
( ) : Number of fl ashing
Wired Remote Controller Display
UTY-RNKY / UTY-RNKG / UTY-RNKYT (3-wire type)
UTY-RNRY / UTY-RNRG (2-wire type)
Touch the [Status].
For more information, refer to the installation manual of the remote controller.
UTY-RLRY / UTY-RLRG (2-wire type)
For more information, refer to the installation manual of the remote controller.
For details on marking the ERROR CODES, refer to the Manual of "Wired Remote Controller".
Wired Remote
Controller Error
FILTER
code
(orange)
lamp (red)
(9)
(1)
(2)
(10)
(2)
(10)
(2)
(3)
(15)
(1)
(6)
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
Error code
Touch the [Next Page] (or [previous page])
Error icon
to switch to other indoor unit information.
Touch the [Error Information].
2-digit numbers are corresponding to
the error code in the preceding table.
Error icon
Error code
Error contents
Connection unit number
error in wired remote
controller system
Indoor unit power supply
abnormal
Indoor unit main PCB
error
Indoor unit
communication circuit
(wired remote controller)
error
Indoor unit heat ex. temp.
thermistor error
Indoor unit air temp.
thermistor error
Indoor unit coil
(expansion valve) error
Indoor unit water drain
abnormal
Outdoor unit
miscellaneous error
RB unit error
DX-kit error

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Utp-vx30aUtp-vx90aUty-vdgx

Table of Contents