Tzidc-110; Ec Type-Examination Test Certificate - ABB TZIDC Operating Instructions Manual

Electro-pneumatic positioner
Table of Contents

Advertisement

Ex relevant specifications

10.2 TZIDC-110

10.2.1 EC type-examination test certificate

Designation:
Type-Examination Test Certificate:
Type:
Standards:
Electrical data
Signal circuit
(Terminal +11 / -12 or + / -)
Voltage
Current
Power
Characteristic
curve
Shutdown contact input
(Terminal +85 / -86)
Mechanical digital feedback
(Terminals Limit1 +51 / -52
or Limit2 +41 / -42)
Local communication
interface (LKS) and program
interface (X5)
IMPORTANT (NOTE)
The local communication interface (LKS) and program interface (X5) may only be operated
outside the potentially explosive area.
60
Temperature class
T4
T5
T6
FISCO power supply
ia/ib for Grp. IIB/IIC
17.5 V
380 mA
5.32 W
rectangular
TZIDC, TZIDC-110, TZIDC-120
II 2 G Ex ia IIC T6
TÜV 02 ATEX 1831 X
Intrinsically safe equipment
EN 50014:1997
EN 50020:1994
Ambient temperature range
In Intrinsic Safety types of protection Ex ia IIC or Ex ib IIC, only
for connection to a certified intrinsically-safe circuit (e.g., FISCO
power supply unit) with max. values based on the following
table:
FISCO power supply
ia/ib for Grp. IIB/IIC
17.5 V
360 mA
2.52 W
trapezoidal
L
negligibly small
i
C
negligibly small
i
In Intrinsic Safety types of protection Ex ia IIC or Ex ib IIC, only
for connection to a certified intrinsically-safe circuit with max.
values
U
= 30 V
i
C
= 3.7 nF
i
L
negligibly small
i
For max. values, see EC-type-examination test certificate
number PTB 00 ATEX 2049 X
Only for connection to a programmer or PC outside the
potentially explosive area.
-40 ... 85 °C
-40 ... 55 °C
-40 ... 40 °C
Barriers or power
supply
ia/ib for Grp. IIB/IIC
24 V
250 mA
1.2 W
Linear
42/18-84-EN