B l o c k i n g E r r o r
F l u e G a s E r r o r
13 - TROUBLE SHOOTING
Low water cutoff sees no water.
Flue temperature sensor sees temperature
3
E 39
higher than 200°F.
Return water temperature sensor sees
temperature higher than 200°F.
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Boiler is powered by three wires, hot, neutral
and ground. E44 displays when neutral wire is
not neutral.
Control board sees power supply frequency not
in range of 59 to 61 Hz.
Boiler power supply ground wire is not
grounded.
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Supply temperature sensor is open. No
continuity.
Return water temperature sensor is open. No
continuity.
Flue temperature sensor is open. No
continuity.
Supply water temperature sensor is shorted.
'0' Ohm
Return water temperature sensor is shorted.
'0' Ohm
Flue temperature sensor is shorted. '0' Ohm
Reset button was pressed too many times.
Fault detected in blower motor system.
Explanation
46
Go to Page For
Troubleshooting
Go to Page 53
Go to Page 54
Go to Page 55
Replace Control
Module
Go to Page 55
Go to Page 56
Go to Page 57
Replace Control
Module
Go to Page 57
Go to Page 58
Go to Page 59
Go to Page 59
Go to Page 60
Go to Page 60
Error Clears in 1-2
minutes
Go to page 56