Service Diagnosis
Description
ELECTRICAL BOX TEMPERATURE RISE (COMPRESSOR OFF)
Supposed Cause
1. Fin temperature rise due to defective outdoor unit fan.
2. Fin temperature rise due to short circuit.
3. Fin thermistor defective.
4. Connector in poor contact.
5. Outdoor unit PCB defective.
Troubleshooting
*Remark:
Refer to Appendix A for thermistor resistance check procedures.(Page 59, item 6.1)
Refer to Appendix A for outdoor fan system check. (Page 65, item 6.8)
Refer to Appendix A for installation condition check. (Page 65, item 6.7)
47
Turn off the unit and turn
on back after 20 mins.
Error again?
Check heat sink thermistor
resistance.
No
Change
Resistance normal?
thermistor.
Yes
Change
No
Heat sink
temperature > A°C?
outdoor
PCB.
Change heat sink or check
outdoor fan condition.
Models
RXB50/60B
ARXN/RXN25/35M
ARXN/RXN50/60M
L3
No
Check outdoor fan.
Yes
Outdoor fan
functioning?
Yes
Heat sink dirty?
Yes
Clean the heat sink.
A°C
80
78
122
Change
No
outdoor
fan motor.
Check
No
installation
condition.