6.3.2 Data Register List
Data register
DT00050
RS485 Device number
RS485
DT00051
Transmission speed
RS485
DT00052
Transmission format
DT00053
RS485 Stop bit
DT00054
RS485 Response time
DT00055
Phase/Wire
DT00056
CT type (2
Primary side current
DT00057
of CT
DT00058
VT ratio
Temperature correction
DT00059
value
DT00070
Auto-off
DT00087
Conversion rate (-P)
DT00093
Conversion rate (P)
DT00094
Password
DT00095
Auto display start
DT00096
Display cycle
DT00097
Luminance
DT00098
Protocol
Name
Unit
-
-
-
-
1ms
-
Rated A
nd
)
(rms)
1A
0.01
0.1℃
1min
0.01
0.01
-
1min
1sec
-
-
Kind of data
Mewtocol: 1 to 99
Unsigned 16bit
Modbus: 1 to 247
DL/T645: 0 to 9999
0: 1200 1: 2400 2: 4800
Unsigned 16bit
3: 9600 4: 19200 5: 38400
Unsigned 16bit
0: 8bit-o 1: 8bit-n 2: 8bit-E
Unsigned 16bit
1, 2
Unsigned 16bit
1 to 99
0: 1P2W 1: 1P3W
Unsigned 16bit
2: 3P3W 3: 3P4W
Unsigned 16bit
1, 5
Unsigned 16bit
1 to 4000
Unsigned 16bit
100 to 60000
Signed 16bit
-100.0 to 100.0
Unsigned 16bit
0 to 99 (0: always ON)
Unsigned 16bit
0 to 9999
Unsigned 16bit
0 to 9999
Unsigned 16bit
0 to 9999
Unsigned 16bit
0 to 99 (0: fix display item)
Unsigned 16bit
1 to 99
Unsigned 16bit
1 to 5 (dark to light)
0: MEWTOCOL 1: MODBUS
Unsigned 16bit
2: DL/T645
41
KW9M Eco-POWER METER
Range
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W