Purpose of PUMP x
Number
Activation
54 / 174
Siemens
Building Technologies
8

Aggregates

8.1

Pump (PUMP x)

8.1.1
Purpose and activation
The PUMP x (pump control) function block controls load-dependent pumps.
Depending on the type of controller, the following pump control choices (PUMP x)
are available:
Controller
Number of PUMP
type
x
RLU202
Max. 2
RLU202
None
RLU222
Max. 2
RLU232
Max. 2
RLU236
Max. 3
For activation, you must assign a switching output (Qx) to pump control (PUMP x).