Page 1
Outdoor unit MTA-76C(H)RN1 MOV-76C(H)N1-C MTA-96C(H)RN1 MOV-96C(H)N1-C MTA-120C(H)RN1 MOV-120C(H)N1-C MTA-150CRN1 MOV-76CN1-C×2 MHB-76C(H)RN1 MOV-76C(H)N1-C MHB-96C(H)RN1 MOV-96C(H)N1-C MFA-76C(H)RN1 MOV-76C(H)N1-C MFA-96C(H)RN1 MOV-96C(H)N1-C MFAT-120CRN1 MOV-120C(H)N1-C Midea reserves the right to discontinue, or change specification or designs at any time without notices and without incurring obligations.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Content Part. 1 General information ....2 Part. 2 Indoor Unit ....... 6 Part. 3 Outdoor Unit ......58 Part. 4 Installation ......66 Part. 5 Controller ......117...
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Part. 1 General information 1. Model Names of Indoor/Outdoor Units ....... 3 2. External Appearance ............ 4 3. Nomenclature ..............5...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 1. Model Names of Indoor/Outdoor Units 1.1 Model names of units with heat pump: Indoor unit Outdoor unit Cooling capacity Type Power Power Model Model MBtu/h supply supply MFA-76HRN1 MOV-76HN1-C 75.1...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 3. Nomenclature 3.1 Indoor unit: M F A T – 120 C R N1 Refrigerant type - N1: R410A Remote controller Function code C: Cooling only H: Heat pump Nominal cooling capacity (120×1,000Btu/h)
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Part. 2 Indoor Unit Duct Type ................7 Floor-standing Type ............ 38...
Page 8
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Duct Type 1. Features ................ 8 2. Specifications ..............9 3. Dimensions (Unit: mm) ..........15 4. Service Space ............. 16 5. Refrigerant circuit ............17 6. Wiring Diagrams ............18 7.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 1. Features High capacity of cooling and heating, and energy saving. Thin size, even can installed at limited place. All round steel shell, for high quality protection of transportation.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 9. Electric Characteristics Indoor Unit Power Supply Model Voltage Min. Max. MTA-76HRN1 220-240V 198V 254V 7.53 1.341 6.02 MTA-76CRN1 220-240V 198V 254V 7.53 1.341 6.02 MTA-96HRN1 220-240V 198V 254V 1.605 7.28...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 1. Features Highly capacity of cooling and heating, and energy-saving. Thin size, even can installed at limited place. All round steel shell, for high quality protection of transportation.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 8. Electric Characteristics Indoor Unit Power Supply Model Voltage Min. Max. MFA-76HRN1 220-240V 198V 254V 0.59 2.773 MFA-76CRN1 220-240V 198V 254V 0.59 2.773 MFA-96HRN1 220-240V 198V 254V 0.59 2.773 MFA-96CRN1 220-240V...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 10. Accessories Name Qty. Shape Usage Owner’s manual Installation manual Remote controller manual Water connective pipe Connect to water drainage pipe Remote controller Remote controller mounting bracket Placed the remote controller...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 1. Specifications Model MOV-76HN1-C MOV-76CN1-C Power supply 380-415V~, 3Ph, 50Hz Ambient temp in cooling ° C 17~52 17~52 Ambient temp in heating ° C -7~24 Rated input (Whole units) 11,700 11,700 Rated current (Whole units) 19.3...
Page 61
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Model MOV-96HN1-C MOV-96CN1-C Power supply 380-415V~, 3Ph, 50Hz Ambient temp in cooling ° C 17~52 17~52 Ambient temp in heating ° C -7~24 Rated input (Whole units) 14,400 14,400 Rated current (Whole units) 23.7...
Page 62
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Model MOV-120HN1-C MOV-120CN1-C Power supply 380-400V~, 3Ph, 50Hz Ambient temp in cooling ° C 17~52 17~52 Ambient temp in heating ° C -7~24 Rated input (Whole units) 17,300 17,300 Rated current (Whole units) 28.6...
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 2. Dimension MOV-76C(H)N1-C, MOV-96C(H)N1-C: (Unit: mm) MOV-120C(H)N1-C (Unit: mm) 3. Service Space MOVA-76H-D, MOVA-76C-D, MOVA-96H, MOVA-96C Note: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 4. Wiring Diagrams MOV-76HN1-C, MOV-96HN1-C, MOV-120HN1-C: Item Name Item Name Item Name Item Name COMP Compressor HEAT(A) Crank RT3A Pipe temp. sensor Transformer FAN1-2 Outdoor fan Current detector Room temp. sensor...
Page 65
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz MOV-76CN1-C, MOV-96CN1-C, MOV-120CN1-C: Item Name Item Name Item Name Item Name COMP Compressor HEAT(A) Crank RT3A Pipe temp. sensor Transformer FAN1-2 Outdoor fan Current detector Room temp. sensor SW1-3 Switch CAP1-2...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 5. Electric Characteristics Outdoor Unit Power Supply Compressor Model Voltage Min. Max. TOCA MOV-76HN1-C 380-415V 342V 438V 17.5 20.5 16.5 0.573 2.613 MOV-76CN1-C 380-415V 342V 438V 17.5 20.5 16.5 0.573 2.613...
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Part. 4 Installation 1. Notes ................67 2. Installation of Duct Type Indoor Units ......68 3. Installation of Floor-standing Type Indoor Units ... 73 4. Installation of Outdoor Units ........75 5.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 1. Notes CAUTION: Install the unit where enough space of installation and maintenance is available. Install the unit where the ceiling is horizontal and enough for bearing the weight of the indoor unit.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 2. Installation of Duct Type Indoor Units 2.1 Installating indoor units As the following picture, when install the indoor unit, select the enough solid and level site with enough space for installation and maintance.
Page 70
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 MTA-120C(H)RN1, MTA-150CRN1: (Unit: mm) When the pandant bolt is fixed in wooden structure, please put rectanglar sticks across the beams, and set pendant bolts. When in the new concrete roughcast environment, please use embedded bolts, embedded pulling plugs and stick harness.
Page 71
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz the installation screws to adjust the horizontality. Finally, Tighten the screws. 2.2 Designing and connecting the duct The duct accessories and materials must be produced by professional manufacturers. Int order to prevent air flow shoting, do not set the air inlet orifice near the air outlet orifice.
Page 72
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 View of air inlet side (Unit: mm) MHA1-150C(H)R, MHA1-192C(H)R: View of air outlet side (Unit: mm) View of air inlet side (Unit: mm) All pipelines must be connected closely and soundly without leak of air. The pipelines must be adiabatic and free from condensation.
Page 73
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 2.3 Install the drainage pipe In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform condensate prevention and heat insulation properly. If it is forecast that high humidity and temperature environment (condensate temperature is over 23°...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 3. Installation of Floor-standing Type Indoor Units As the following picture, when install the indoor unit, select the enough solid and level site with enough space for installation and maintance.
Page 75
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz There is natural drain, it is should be confirmed that the height of drain pipe is not higher than water collection tray. The number of bends and folds of the drain pipe should not exceed 2. Try to avoid bends to prevent trash accumulation.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 4. Installation of Outdoor Units When installing the unit, leave a space for maintenance shown in the following figure. Install the power supply at the side of the outdoor unit.
Page 77
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz The distance of the foundation bolt is shown in following picture. MOV-76C(H)N1-C, MOV-96C(H)N1-C, MOV-120C(H)N1-C As the following shown picture, leave an interval between the multi-outdoor unit. Snow protection facilities must be installed in the snowfall areas. In order to prevent influence caused by snow, set up raised pavilion, and install snow protection sheds at the air inlet and air outlet.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 5. Connection of Refrigerant Pipe Schematic diagram of connection between indoor unit and outdoor unit: MTA-76C(H)RN1 + MOV-76C(H)N1-C MTA-96C(H)RN1 + MOV-96C(H)N1-C MTA-120C(H)RN1 + MOV-120C(H)N1-C MTA-150CRN1 + MOV-76C(H)N1-C (2 sets)
Page 79
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz MFA-76C(H)RN1 + MOV-76C(H)N1-C MFA-96C(H)RN1 + MOV-96C(H)N1-C The refrigerant pipe adapter is located inside the outdoor unit. So remove the right front board first, totally three pieces of M5 screw. ...
Page 80
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 All connections between indoor unit and outdoor unit are copper-to copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. Do not use soft solder.
Page 81
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Precaution should be taken to prevent heat damage to the valve by wrapping a wet rag around it. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit.
Page 82
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
Page 83
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Use the refrigerant in the outdoor unit to expel air. Screw up the pipe nuts at A, B, C and D completely. Loosen and remove the square-head cover of valves A and B, rotate the square-head spool of valve B counter-clockwise for 45 degrees and stay for about 10 seconds, and then close the spool of valve B tightly.
Page 84
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Use a vacuum pump Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose of the manifold valve to the maintenance orifice of valve A (Tighten both valve A and valve B).
Page 85
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz picture. Procedure of opening the valve: Open the square-head cover, use a spanner to capture the square head and open it thoroughly. Then tighten the square-head cover. Procedure of closing the valve: Same as the procedure of opening the valve, but rotate the spanner clockwise thoroughly.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Calculate out the refrigerant density: )] ≤ Density threshold: 0.3kg/m [A (kg)] / [B (m Measures against crossing of the refrigerant density threshold. In order to keep the refrigerant density below the threshold value, please install a mechanic ventilation device.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz the ceiling with slab, ceiling which is in the same environment as the outdoor air. It is necessary to apply 10mm or thicker adiabatic wool (16~20kg/m ) to the refrigerant pipe and the drain pipe in addition to applying the general heat insulation materials.
Page 88
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Upon completion of wire connection, double check it and then connect the power supply. An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
Page 89
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Medium static pressure duct: Type Indoor unit Outdoor unit Model MTA-120C(H)RN1 MOV-120C(H)N1-C Power 220-240V~, 1Ph, 50Hz 380~400V~, 3Ph, 50Hz Switch capacity of the main 40A/20A 60A/40A power supply / Fuse Indoor unit power cable 3×2.5mm...
Page 90
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Floor-standing type: Type Indoor unit Outdoor unit MFA-76C(H)RN1 MOV-76C(H)N1-C Model MFA-96C(H)RN1 MOV-96C(H)N1-C Power 220-240V~, 1Ph, 50Hz 380~415V~, 3Ph, 50Hz Switch capacity of the main 20A/10A 60A/40A power supply / Fuse Indoor unit power cable 3×2.5mm...
Page 91
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 7.3 Schematic diagram Single outdoor unit: Double outdoor units:...
Page 92
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 7.4 Electric wire diagram When connect the wire, pay attention to the phase sequence of the power supply. If the phase sequence is reversed, the compressor will not start. Meanwhile, the fault indicator of the outdoor electric control board will light up.
Page 93
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz MTA-150CRN1: Notes: Please identify outdoor main unit and auxiliary unit. Only adjust the dial on PCB board of outdoor unit as follows, otherwise incorrect adjustment may cause malfunction. Signal wire of indoor unit connects to outdoor main unit only and the control command to outdoor auxil unit is sent by COM wire connecting with main unit.
Page 94
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 MFA-76HRN1, MFA-96HRN1: MFA-76CRN1, MFA-96CRN1, MFAT-120CRN1:...
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 8. Duct Design Scheme Examples of construction and ventilation pipeline design scheme (Flowering hidden series.) Construction and ventilation pipeline design scheme...
Page 96
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Methods of configuring and selecting installation Material name Characteristics, advantages and other contents 1. Install the filter at the main body grille in case the store height is low, and at the main body of the indoor unit in case the store height is high.
Page 97
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 1. Fixed model that diffuses air at a 360 angle. 2. The outline size should increase when the air volume is over 350CMH. (For above 303), i.e., when about 9 diffusers are required, the outline size should increase.
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 1. Low noise compared with other air outlets. Applicable to tall buildings that require a long distance of air conditioning. 2. Select the ventilation pipe connection caliber according to the distance and the air speed.
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Use the remote controller or wired controller to let the air conditioner run in the cooling mode. Inspect the following items according to the operation manual. If any fault occurs, remove the fault first.
Page 100
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 ADJUST: UP and DOWN This button is also called Temperature adjustment key. UP: For increase temperature. Any time press the key, temperature will increase one Celsius degree. When press the key last for more than 1 second, the temperature will increase by 1°...
Page 101
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz the light extinction, while the status of selected mode icon is light-on instead of flashing. Power on for the first drive up, after press the ON/OFF, default mode of FAN appear. If...
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 11. Trouble shooting 11.1 Phenomena not attributable to faults of air conditioner The system does not run. After pressing the ON/OFF button, the system does not run immediately. ...
Page 103
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Squeak may occur when the air conditioner starts or stops running. That is the sound raised because the plastic assemblies inflate or deflate when the temperature changes. Dust is blown out of the indoor unit.
Page 104
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Symptom Possible causes Way of handing Power supply fails. Operate it after power supply resumes The power switch is not and connect the power supply properly. connected. The system does The fuse blows out or the circuit Replace the fuse or check whether not run.
Page 105
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Symptom Possible causes Way of handing The refrigerant is excessive or Detect leak, and fill the refrigerant of a deficient. correct quantity. Air or non-condensable gas Make a vacuum again and fill the exists in the refrigerant loop.
Page 106
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 The display disappears. Symptom Check item Cause After a while the Check whether the time set on The air conditioner stops running ON/OFF display the timer has expired. because the set time has expired.
Page 107
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 11.4 Duct type indoor unit malfunction and protection codes Names of indicators in receiving kit Display content Fault or protection meaning All lamps flashing at Lack of neutral line. Timer lamp flashing T1, room temperature sensor, fault of open circuit, short circuit.
Page 108
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Timer lamp flashing at 5Hz, Operation lamp flashing at 5Hz Defrosting lamp flashing at 5Hz For these series products, if the condenser temperature sensor malfunction is displayed, it is enough to check whether wiring has problem. If the wiring is correct, the PCB should be replaced.
Page 109
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz E1, E2...
Page 110
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 11.6 Outdoor unit malfunction and protection codes Type LED1 LED2 Phase sequence protection ◆ ●★ Communication failure ◆ ●●★ Outdoor condenser temp. sensor error ◆ ●●●★ Outdoor ambient temp. sensor error ◆...
Page 111
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Phase sequence or lack of phase Communication error...
Page 112
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Condenser temperature sensor error Ambient temperature sensor error Hi-temperature protection of compressor discharger...
Page 113
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz System low pressure protection...
Page 114
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 System high pressure protection Current overload protection...
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz High temperature protection of condenser 12. Maintenance Operation required before leaving the unit idle for a long period. Let the air conditioner run in the fan mode for about half a day, and let its interior be fully dry.
Page 116
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 and then cut off the power supply. Startup after a long period out of service. Check the following issues: Check whether the air inlet or outlet of the indoor unit and outdoor unit is blocked.
Page 117
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz If the stain is heavy and difficult to clean, replace the filter. Do not replace the power cable without permission. If the power cable is damaged, specialized power cable must be used as substitute.
Page 119
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 1. Wireless Remote Controller (Standard) 1.1 Remote controller specifications Model R51/E Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it Gets 11m) Environment Temperature Range -5°...
Page 120
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 2. MODE Select Button: Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates: 3.
Page 121
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 1.3 Names and functions of indicators on remote controller ①TRANSMISSION Indicator: This indicator lights when remote controller transmits signals to indoor unit. ② MODE Display: Show the current operation modes-- AUTO, COOL, DRY and HEAT. HEAT is only available for heat pump model.
Page 122
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 ※ To install batteries, slide back the cover of the battery compartment and install the batteries according to the directions (+and -) shown on the Remote Controller. ※ To replace the old batteries, use the same method as mentioned above.
Page 123
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz HEATING mode, the most comfortable settings are 28 or below. ° C ※ Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW. ※ Push the ON/OFF button. The operation lamp lights and the air conditioner start to operate per your settings.
Page 124
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 ※ Push the TIMER button and the remote controller will show the last set time for the START operation and the signal "h" will be shown on the display panel. You are now ready to readjust the TIMER OFF to stop the operation.
Page 125
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 2. Keep the Remote Controller away any liquids. 3. Protect the Remote Controller from high temperatures and exposure to radiation. 4. Keep the indoor receiver out of direct sunlight or the air conditioner may malfunction.
Page 126
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 2.2 Wired controller outlook 2.3 Operation instructions 1) Remote signal receiving function: the wired controller can be a remote signal receiving device, it is possible to use the wireless remote controller to control the air conditioner through the wired controller when the system have been powered on.
Page 127
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 3) Set the operating mode Press the mode button to set the operating mode, after each button press the operating mode will circle as follow: Notes: When the controller has been set to cool only, then there is no HEAT mode.
Page 128
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Under the timer on setting status, press the timer/clock setting button , then enter into the timer off setting status, and the screen will display The setting method of timer off is the same as the timer on.
Page 129
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Under the locking state, the wired controller will not respond to the buttons pressing and the control instruction from the wireless remote controller. Simultaneously press the temperature adjusting buttons again can cancel the locking state.
Page 130
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 2.4 Installation of wired controller 1) Safety precaution Stated below are important safety issues that must be obeyed. Confirm there is no abnormal phenomena during test operation after complete. ...
Page 131
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 3) Supplied assemblies on the site Qty (Embedded Specification (Only Name Remarks into wall) for reference) 4-core shielded cable 0.5mm ×4 The longest is 15m. 86 Electrician box Wiring tube (Insulating sleeve and tightening screw.)
Page 132
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Wiring principle sketch: Wiring figure: Connect two terminals of embedded 4-core shielding wire with the switching wires of wired controller and signal receiving board. Make sure the sequence of 4 terminals (A, B, C and D) should correspond to the wire sequence of signal switching wires (A, B, C and D).
Page 133
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Use straight head screwdriver to insert into the buckling position in the bottom of wired controller, and spin the screwdriver to take down the back cover. Pay attention to spinning direction, otherwise will damage the back cover.
Page 134
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Use cross head screws to fix the wired controller bottom cover in the electrical box through the screw bar. Make sure the wired controller bottom cover is on the same level after installation, and then install the wired controller back to the bottom cover.
Page 135
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Avoid the water enter into the wired controller, use trap and putty to seal the connectors of wires during wiring installation. When under installation, reserve certain length of the connecting wire for convenient to take down the wired controller while during maintenance.
Page 136
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Step2: The value of the first code ‘X’ is ‘0’, press the temperature setting buttons to adjust the second code value. Step3: After setting the second code value, press Quiet/OK button to switch the first code to the next value.
Page 137
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 3. Centralized Controller: MD-CCM03(A) (Optional) 3.1 Centralized controller specifications Model MD-CCM03(A) Power Supply Voltage 220~240V 50Hz 1Ph Ambient Temperature Range -15° C~43° C Ambient Humidity Range RH40%~RH90% Performance Features 1. System composition, centralized control.
Page 138
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 single-machine setting is selected, the operation is performed for the air conditioner of the current address only. If the remote controller of the air conditioner is locked currently, issue the lock command; otherwise, send the lock command. If the single-machine mode is not selected, and the remote controller of one or more currently selected air conditioners is locked, issue the unlock command;...
Page 139
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz the key again, and the operation will be performed for all air conditioners in the network. Press it repeatedly to shift between single setting and global setting. 4) QUERY: Any time when pressing the key, the selected operation mode is to query the operation status of the air conditioner.
Page 140
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 previous air conditioner will be displayed. If it is currently on the first machine, press it again, and the data of the last machine will be displayed. If this key was held down, the address will decrease one by one.
Page 141
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz the last page will be displayed. In the setting mode, every time when pressing the key, if it is in the temperature regulation mode, the set temperature will decrease by 1° C (or 2° C) until the lowest allowed set temperature.
Page 142
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 result is the same as the result of restoring power-on after power failure. 16) ON/OFF: Any time when pressing the key, the centralized startup/shutdown operation is performed for all current in-service air conditioners in the centralized controller network. If all in-service air conditioners in the network are in the power-off status, press the key to perform the startup operation.
Page 143
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz : The matrix is composed of 4×16 grids and each grid is composed of two blocks of different sizes. The matrix include horizontal coordinates 00-15 and vertical coordinates 00+, 16+, 32+ and 48+, which indicate the address of the indoor unit.
Page 144
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 controller is a master, and the air conditioner is a slave. In the LAN composed of computer and centralized controller, the computer or gateway is a master, and the centralized controller is a slave.
Page 145
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz indicator goes off. If an in-service air conditioner in the network is faulty, or the centralized controller network itself is faulty, the indicator will blink at 2Hz. If one or more in-service air conditioners in the network are running, including under setting of timing start or shutdown, the indicator will be luminous.
Page 146
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 until the foregoing switch is turned off. If the foregoing two switches are turned on concurrently, the emergent shutdown switch shall have preference. 3.5 General display data entries 1) General display data is displayed in all display pages.
Page 147
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz Indoor temperature display: display range: 00~99° C. The indoor temperature is displayed concurrently. If the temperature is higher than 99° C, 99° C will be displayed. If the temperature value is invalid, ‘--‘ will be displayed.
Page 148
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 In the matrix, the bid dots from (00, 16+) to (15, 32+) are luminous, and the small dots are not luminous. It indicates the 32 air conditioners with the addresses from 16 to 47 are powered off.
Page 149
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz In the matrix, only the big and small black dots at (00, 00+) and (01, 00+) are luminous. It indicates the in-service and power-on status of the air conditioners with the addresses of 00 and 01.
Page 150
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 The centralized controller communicates with the computer normally. Fault code table: Fault code Fault content Other faults Outdoor unit fault protection Over-current of compressor (4 times) Fault of communication between main board and display board...
Page 151
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 3.6 Installation The wireless remote controller is the standard controller for split series air conditioner. Wired controller as optional controller can directly be connected with the display board of the indoor units.
Page 152
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 Dimension of MD-NIM01 Connect the network interface module with the port CN20 in the main PCB board of indoor unit through the signal wire, which is as the attachment of the module.
Page 153
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz According to size of the hole in controller body, fix the controller on the place as needed. (Unit:...
Page 154
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 3) The wire connection...
Page 155
MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz 4) System wiring instruction Wiring diagram of building network air conditioning system Wiring diagram with good communication effect Wiring diagram with poor communication effect (not recommended because it may lead...
Page 156
Midea R410A T3 Top-discharge Split Type Series 50Hz MCAC-UTSM-201501 System wiring diagram of centralized monitoring and indoor unit of air conditioner Both of the following wiring modes of centralized monitor and indoor unit are applicable: (Quantity of indoor units connected with each centralized monitor is less than or equal to 64).