Capacity tables

4 - 2 Cooling capacity tables

EBHQ011-016BA6V3
Maximum Cooling Capacity
SYMBOLS
CC
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
HC
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
PI
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
LWE
: Leaving Water Evaporator temperature (°C)
LWC
: Leaving Water Condensor temperature (°C)
Tamb
: Ambient temperature (°C) RH=85%
90
• Monobloc • EBHQ011-016BA6V3
• Daikin Altherma • Monobloc
NOTES
1
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
2
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
3
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For ERHQ011-16AAW1 models only: if Tamb < 4°C: bottom plate heater power
input to be added = 95 W
Notes:
- For the model with heatertape (*RLQ): when ambiernt temperature becomes lower than [F-02] (default = 3°C) bottom
plate heater power input to be added = 95W
- [F-02] = BPH ON temp for more details see installationmanual of indoor unit.
3TW58012-1A