To wire the remote core processor to the transmitter:
1. Use one of the following methods to shield the wiring:
Installation method
Unshielded wiring in continuous metallic conduit that provides 360°
termination shielding for the enclosed wiring
A user-supplied cable gland with shielded cable or armored cable,
terminate the shields in the cable gland. Terminate both the armored
braid and the shield drain wires in the cable gland
A Micro Motion-supplied cable gland at the core processor housing
2. Do one of the following:
3. Identify the components shown in
4. Remove the core processor lid.
5. Slide the gland nut and the clamping insert over the cable. See
Installation Manual
If you are using shielded cable, prepare the cable and apply shielded heat shrink
as described in Step 6. The shielded heat shrink provides a shield termination
suitable for use in the gland when using cable whose shield consists of foil and not
a braid.
If you are using armored cable, prepare the cable as described in Step 6, but do
not apply heat shrink – omit Steps 6d, e, f, and g.
Figure
2-3.
Wiring
Procedure