General Overview - ABB AMVAC Technical Manual

5/15/27 kv ansi magnetic mechansim vacuum circuit breaker
Hide thumbs Also See for AMVAC:
Table of Contents

Advertisement

AMVAC breaker

General overview

The AMVAC breaker is a magnetically actuated and latched
breaker capable of a high number of operations due to its
simplified design. Fully compliant with IEEE Standards C37.04,
C37.06 and C37.09, the AMVAC breaker is a great fit for many
applications.
Features
− Mechanical operations counter
− Optional roll-on-floor design
− Open, closed, ready/not ready lights and pushbuttons
− Maintenance-free magnetic actuator
Available AMVAC breaker ratings
Voltage class
Nominal voltages
kV
kV
2.4, 4.16, 4.8
5
8.25
4.8, 6.9, 7.2
6.9, 7.2, 8.4, 11, 12,
15
12.47, 13.2, 13.8,
14.4
27
20.78, 21.6, 22.86,
23, 23.9, 24.94
Continuous current Short circuit/with-
stand (2 sec)
A
kA, rms
1200, 2000, 3000
25
31.5
40
50
1200, 2000, 3000
40
1200, 2000, 3000
25
31.5
40
50
1200, 2000
16
25
Close and latch
BIL (lightning im-
pulse withstand)
kA, peak
kV, crest
65
60
82
104
130
104
95
65
95
82
104
130
42
125
65
Low frequency
withstand (Hi-Pot)
kV, rms
19
36
36
60
AMVAC | SafeGear HD 3

Hide quick links:

Advertisement

Table of Contents