9.6 — 0K9243-A 48 kW (5.4 L) Page 1 of 2
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
NEGATIVE GROUND
508
[20.0]
240
[9.4]
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
RADIATOR/EXHAUST
DISCHARGE AIR
55
[2.2]
FUEL LINE CONNECTION
LEFT SIDE VIEW
3/4" NPT FEMALE COUPLING

Installation Guidelines for Spark-Ignited Stationary Emergency Generators

SERVICE ITEM
OIL FILL CAP
AIR INTAKE
OIL DIP STICK
BATTERY 12V
(BOTH SIDES)
OIL FILTER
GRP 26
OIL DRAIN HOSE
RADIATOR DRAIN HOSE
COOLANT RECOVERY BOTTLE
P/N: 058208
RADIATOR FILL CAP
AIR CLEANER ELEMENT
SPARK PLUGS
MUFFLER
DRIVE BELT
FAN BELT
BATTERY
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PART LISTINGS.
721.4
CENTER OF GRAVITY
(SEE NOTE 5)
TOP VIEW
CIRCUIT BREAKER
SEE NOTE 3
670
[26.4]
ENCLOSURE
ENGINE/KW
MATERIAL
5.4L/48KW
AL
5.4L
RIGHT SIDE
LEFT SIDE
LEFT SIDE
RIGHT SIDE
LEFT SIDE
LEFT SIDE
ROOF TOP
EITHER SIDE
EITHER SIDE
SEE NOTE 11
EITHER SIDE
SEE NOTE 11
RIGHT SIDE
REAR ENCLOSURE
1170
COVER PANEL
[46.1]
SEE NOTE 4
OVERALL
HEIGHT
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
888 [35.0]
OVERALL WIDTH
REAR VIEW
WEIGHT DATA
WEIGHT
WEIGHT
SHIPPING WEIGHT
GENSET ONLY
SHIPPING SKID
KG [LBS]
KG [LBS]
KG [LBS]
705 [1555]
44 [98]
750 [1653]
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2256 (88.8") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
47 [1.8]
1857 [73.1] TYP
TYP
1950 [76.8] OVERALL LENGTH
VICE ACTION LATCH,
ONE PER DOOR,
ONE LIFT OFF
759 [29.9]
DOOR PER SIDE
DOOR TYP
OF GENERATOR
58
[2.3]
TYP
59

Advertisement

Table of Contents