Viessmann VITODENS 222-F Installation And Service Instructions Manual page 116

Gas condensing storage combi boiler
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
EF
X
F0
X
F1
X
F2
X
116
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner blocked Internal fault
X
Burner in a fault
state
X
Burner in a fault
state
Cause
Measures
Flame is lost
Check gas supply
immediately
(gas pressure and
after it has
gas flow limiter).
built (during
Check flue gas/
the safety
ventilation air sys-
time).
tem for flue gas
recirculation.
Check ionisation
electrode (replace
if required):
■ Distance to
burner gauze
assembly (see
page 38)
■ Contamination of
electrode
Press reset button
R.
Replace control
unit.
Flue gas tem-
Check heating sys-
perature lim-
tem fill level. Vent
iter has
the system.
responded.
Press reset button
R after flue system
has cooled down.
Temperature
Check heating sys-
limiter has
tem fill level. Check
responded.
circulation pump.
Vent the system.
Check temperature
limiter and con-
necting cables.
Press reset button
R.