6
WIRING
6.1

Wiring Preparations

Wiring procedure

Before wiring, make sure that the source power supply is off.
1.
Prepare the parts for wiring.
Prepare crimp terminals and cables needed for wiring. (Page 92 Cable Connecting Procedure)
2.
Wire the power supply terminals.
For AC power supply type, connect the cables to the power [L] and [N] terminals.
For DC power supply type, connect the cables to the power [+] and [-] terminals.
Provide the protection circuit described in this chapter for the power supply circuit. (Page 96 Power Supply Wiring)
3.
Perform class D grounding (grounding resistance: 100  or less) for the ground [
Connect the grounded wire to the terminal. (Page 95 Grounding)
4.
Wire the input [X] terminal.
Select sink or source in the following wiring.
In the case of AC power supply type
• For sink input, connect [24V][S/S] terminal
• For source input, connect [0V][S/S] terminal
In the case of DC power supply type
• For sink input, connect [+][S/S] terminal
• For source input, connect [-][S/S] terminal
Connect sensors and switches to the terminals. (Page 102 Input Wiring)
5.
Wire the output [Y] terminal.
Connect the load to terminals. (Page 114 Output Wiring)
6.
Wire built-in analog I/O terminal blocks.
Connect analog I/Os to terminals. (Page 129 Analog Wiring)
7.
Wire the built-in RS-485 communication terminal blocks and Ethernet communication connectors.
MELSEC iQ-F FX5 User's Manual (Ethernet Communication)
MELSEC iQ-F FX5 User's Manual (Serial Communication)
MELSEC iQ-F FX5 User's Manual (MODBUS Communication)
8.
Wire intelligent function modules, expansion boards, and expansion adapters.
MELSEC iQ-F FX5 User's Manual (Serial Communication)
MELSEC iQ-F FX5 User's Manual (MODBUS Communication)
User's manual for each intelligent function module
] terminal.
6 WIRING
6.1 Wiring Preparations
6
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5u seriesMelsec iq-f fx5u-u-hw-e09r536

Table of Contents