e. Select I/O Modules.
f. In the right pane, right-click the module, then click Request Swap Clear.
g. Click the Alerts tab.
h. Right-click the alerts for the temperature sensor and I/O modules, then click Acknowledge.
NOTE: The alerts may not appear immediately. If the alerts do not appear, wait 10 seconds
and then click Refresh.
Next steps
Use SupportAssist to send diagnostic data to Dell Technical Support.

Replace Both Storage Controllers in Succession

Use this procedure to replace both storage controllers, one at a time.
Prerequisites
1.
Use SupportAssist to send diagnostic data to Dell Technical Support.
2.
Shut down the left storage controller.
About this task
This procedure is useful if you are swapping out degraded, but still operational, storage controllers.
Steps
1.
Make sure all of the cables are labeled.
2.
Disconnect all of the cables from the left storage controller.
3.
Remove the battery from the left storage controller.
4.
Push down on the release tab of the top storage controller and pull the release lever away from the
chassis.
NOTE: Wait until all of the storage controller indicators are off before removing the storage
controller.
5.
Grasp the release lever and pull the storage controller away from the chassis.
40
Replacing SCv2080 Storage System Components