Ceiling Opening Dimensions And Hanging Bolt Location - LG LT-D5480HL Service Manual

Ceiling cassette air conditioner
Table of Contents

Advertisement

2. Ceiling opening dimensions and hanging bolt location

• The dimensions of the paper model for installing are
the same as those of the ceiling opening dimen-
sions.
CAUTION
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to
damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain
direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
NOTE:
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
Ceiling
Level gauge
Air conditioner
Take enough
distance
875 (Ceiling opening)
785(Hanging bolt)
45
840 Unit size
Cooking table
–15–
45
Unit:mm
Ceiling board
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lt-d5480haLt-d5480clLt-d5480ca

Table of Contents