The TH147 and TH148LE thermostats can be used to control:
• a gas, fuel oil or electric furnace - 2 or 3 wires
• a central air conditioner - 2 or 3 wires
• a hot water system with or without pump - 2 wires
• a millivolt system - 2 wires
• a central heating and cooling system - 4 or 5 wires
Attention: These thermostats are not compatible with heat pumps
or multi-stage systems.
Display
System operating
Fan operating
mode selector
mode selector
Functions
Heating/cooling control
Fan control
Programmable cycle lengths
Temperature display in °C or °F
Backlit display
Battery replacement indicator
Unoccupied mode activated remotely (requires Aube's CT240)
Interchangeable faceplates (titanium, charcoal & taupe)
TH147 and TH148LE
TH147 & TH148LE
Electronic Thermostats
Installation
and User Guide
Adjustment
buttons
Backlight
button
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2. Installation
Note: The installation must be performed by an electrician or a qual-
ified installer.
2.1 Removing the Old Thermostat
IN ORDER TO AVOID ANY RISK OF ELECTRIC SHOCK, CUT
POWER TO THE HEATING/COOLING SYSTEM.
Remove the old thermostat to access the wires.
Attention: If the old thermostat was mounted onto an electrical box,
it might have been powered by 120/240 volts. In this case, the
TH147 or TH148LE thermostat cannot be used.
Identify and label each wire (with the corresponding letter on
the wire terminal) and remove it from its terminal.
If necessary, strip the end of each wire
(maximum of 6 mm).
Wrap the wires around a pencil to prevent
them from falling into the wall.
If the hole in the wall is too big, insulate it
using a non-flammable material in order
to avoid air draughts behind the thermostat.
2.2 Installing the New Baseplate
For a new installation, choose a location approximately 1.5 m
(5 feet) above the floor and on an inside wall. Avoid draughty
areas (top of staircase, air outlet, etc.), dead air spots (behind
doors), direct sunlight or areas near concealed pipes or chim-
neys.
Remove the thermostat faceplate.
Loosen the locking screw in order to separate the thermostat
from its baseplate (the screw cannot be completely removed).
Gently tilt the thermostat upwards.
Mark and bore the appropriate mounting holes (or use the
existing holes). Insert the plastic anchors.
Pass the wires through the opening of the baseplate and fix the
baseplate to the wall using the screws provided.
400-147-010-C
27/11/06
1/4

Advertisement

loading

Summary of Contents for Aube Technologies TH147

  • Page 1 1. Introduction The TH147 and TH148LE thermostats can be used to control: • a gas, fuel oil or electric furnace - 2 or 3 wires • a central air conditioner - 2 or 3 wires • a hot water system with or without pump - 2 wires •...
  • Page 2 Note: Remove the red jumper wire between terminals Rc and Rh. 2.4 Remote Control Input (TH148LE only) The TH148LE thermostat has an input to which a CT240 telephone controller (optional) or any other remote control system (e.g., home automation) can be connected. When the input receives a 12-VDC signal, the thermostat switches from its current mode to the unoccupied mode and vice versa when the signal is removed.
  • Page 3 The new setpoint will be main- tained for 2 hours, then the thermostat will return to the setpoint of the unoccupied mode. The 3.6 Low-Battery Indicator An icon appears when the batteries need replacement.
  • Page 4 Compressor short-cycle protection (minimum off time): 5 minutes Dimensions: 127 mm x 75 mm x 28 mm (5 in. x 3 in. x 1 in.) TH147 and TH148LE 6. Warranty Aube warrants this product, excluding battery, to be free from...