10.3.8 P1(over voltage or too low voltage protection) diagnosis and solution.
Is the power supply good?
10.3.9 P2(temperature protection of compressor top) diagnosis and solution.
Does compressor
operate?
YES
Is refrigerant
circulation
volume normal?
NO
Charge refrigerant
Is abnormality
the same after
gas charging?
NO
10.3.10 P4(inverter compressor drive error) diagnosis and solution.
Is the connection of
compressor good? Is the
wiring sequency right? The
voltage range proper?
Replace the outdoor E-box.
If the problem comes to
again, check coil resistance
of inverter compressor, is it
0.71ohm?
YES
NO
Check the outdoor
main PCB. Is there
some problem?
YES
NO
Is the connection
good?
YES
Is protector
normal?
YES
YES
NO
NO
Be sure the power supply is
normal when using the units
Replace the outdoor e-box.
NO
Reconnect and retest.
NO
Replace the protector.
Replace the outdoor PCB.
Check refrigerant system
(such as clogging of capillary,
Reconnect and retry
Replace inverter compressor