Download Print this page
Omega Engineering PSW400 Instruction Sheet

Omega Engineering PSW400 Instruction Sheet

Pressure switches

Advertisement

Quick Links

®
PSW400
Pressure Switches
INSTRUCTION
SHEET
INSTALLATION INSTRUCTIONS FOR OMEGA
PSW400 – H
O
2
B
11
/
(17)
G
16
C
Clearance
Required for
Cover Removal
3/4 NPT
TYP
A
D
E
F
H
Ø.31 (8)
I
4 HOLES
J
STANDARD RANGES
10, 30, 60, 100 & 150 IN.H
A
B
C
D
E
F
G
1
7
1
5
11
8
5
3
1
2
2
4
8
8
16
16
16
(206) (127) (98) (27) (59) (51) (17) (121) (130) (140) (70) (135)
The OMEGA
PSW400 Series pressure
®
control is a precision device which fea-
tures a snap-action switch. Fixed dead-
band is available with dual SPDT indepen-
dently adjustable switches with various
electrical ratings. Adjustable deadband is
available with various electrical rating.
The PSW400 Series snap-action pressure
switch offers a NEMA 7/9 explosion-proof
enclosure, Class I, Div. 1 & 2, Groups B, C
& D and Class II, Div. 1 & 2, Groups E, F
& G. The enclosure is an epoxy-coated
aluminum casting.
INSTALLATION
This control is a precision instrument and
should never be left with internal compo-
nents exposed. During installation, insure
that covers are in place and conduit open-
ings are sealed.
MOUNTING
Four holes in the bracket supplied are used
in surface mounting of the control. Loca-
tion of these holes is shown on the general
dimension drawings. Mount on a vibration-
free surface or pipe. When tightening con-
trol to pressure line, always use the
wrench flats or hex on the pressure connec-
tion. Never tighten by twisting the case.
ELECTRICAL CONNECTION
Remove top cover; the cover unscrews
M0534/0902
SERIES PSW400 PRESSURE SWITCHES
PSW400 – psi
G
K
A
L
L
1/4 NPT
O
2
H
I
J
K
L
A
3
1
1
3
5
5
5
2
5
7
7
4
8
2
4
16
16
(189) (127) (98) (27) (59) (33) (17) (121) (140) (70) (59)
CCW. Wire directly to the switch according
to circuit requirements.
CONDUIT CONNECTIONS
Two
3
4
with a plug., the other with a cap. It is rec-
ommended that Teflon tape or other sealant
be used on conduit bushing or plug threads
to ensure integrity of the enclosure.
SETPOINT ADJUSTMENTS
Dual Setpoint Switch
Remove front cover, which is held in place
by two screws. There are two range adjust-
ing wheels. The adjusting wheel on the left
(labeled A) controls the left switch, the
adjusting wheel on the right (labeled B)
controls the right switch. The switches are
set independently.
Note:The units are calibrated at the factory
such that for proper operation, switch B
setpoint must be set higher than switch A
setpoint.
For setpoint adjustment to within ±1% of
nominal range, mount the switch on a cal-
ibration stand, and use a suitable refer-
ence such as an OMEGA process gauge
(Model PGH or PGJ), or test gauge (Model
PGT). Monitor switch with a suitable pilot
light or meter.
Pressurize the system to the required set-
11
/
(17)
16
B
Clearance
Required for
Cover Removal
3/4 NPT
TYP
D
E
F
Ø.31 (8)
4 HOLES
C
1/4 NPT FEMALE
H
I
STANDARD RANGES – psi
0/15
0/30
0/100 0/400
0/20
0/60
0/200 0/600
B
C
D
E
F
G
H
I
5
3
7
1
1
2
5
1
5
11
4
3
5
1
8
16
16
16
16
4
˝ NPT holes are provided, one fitted
PSW400 – Pipe Mounting Bracket
J
2
13
/
(71)
16
K
J
K
2
3
2
5
2
4
16
point and turn the adjusting wheel until
the switch changes mode. When the set-
point has been achieved, raise and lower
the pressure to insure that the setpoint is
correct. This must be done for both set-
point A and setpoint B.
ADJUSTABLE DEADBAND SWITCH
Remove front cover, which is held in place
by two screws. The adjusting wheel
labeled A controls the reset point of the
switch. The adjusting wheel on labeled B
controls the setpoint of the switch.
Note:The units are calibrated at the factory
such that for proper operation, setpoint B
is always higher than reset point A .
For accurate setpoint adjustment, mount
the switch on a calibration stand, and use
a suitable reference such as an OMEGA
process gauge (Model PGH or PGJ), or test
gauge (Model PGT). Monitor switch with a
suitable pilot light or meter. Pressurize the
system to the required setpoint. Move
adjusting wheel on spring B until switch
changes mode. The lower pressure to the
reset point, move adjusting wheel on
spring A until the switch changes mode.
Raise and lower pressure to insure that
setpoint is correct. Repeat as necessary.
M0534 8/99 DPS-5C-1P-10/99 Printed in U.S.A.
®
Requires Standard
5
/
(8) Dia. U-Bolt
16
Not Furnished
PIPE MOUNTING
BRACKET
2
7
/
(56)
32
Ø.38 (10)
U-Bolt Holes
2
/
(71)
13
16

Advertisement

loading

Summary of Contents for Omega Engineering PSW400

  • Page 1 Adjustable deadband is available with various electrical rating. The PSW400 Series snap-action pressure switch offers a NEMA 7/9 explosion-proof enclosure, Class I, Div. 1 & 2, Groups B, C & D and Class II, Div. 1 & 2, Groups E, F &...
  • Page 2 MADE IN OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.