Omega DRG-AR-TC Instruction Sheet

Field configurable limit alarm

Advertisement

Quick Links

SPECIFICATIONS
Stability
Temperature: ±0.05% of full
Inputs
scale/°C, max.
Range: See Table 1
Common Mode Rejection
Impedance: >1 Megaohm
DC to 60Hz: 120dB
Input Bias Current (burnout
Isolation
detection): <1.5 microamp
1800VDC between contacts,
Overvoltage: ±10V differential
input and power
Common Mode (Input to Ground):
EMC Compliance (CE Mark)
1800VDC, max.
Emissions: EN50081-1
LED Indicators
Immunity: EN50082-2
Input Range (Green)
Safety: EN50178
>110% input: 8Hz flash
Humidity (Non-Condensing)
<0% input: 4Hz flash
Operating: 15 to 95% (@45°C)
Setpoint (Red):
Soak: 90% for 24 hours (@65°C)
Tripped: Solid red
Temperature Range
Safe: off
Operating: 0 to 55°C (32 to 131°F)
Limit Differentials (Deadbands)
Storage: -15 to 70°C (5 to 158°F)
0.25% to 5% of span
Power
Response Time
Consumption: 1.5W typical,
Dynamic Deadband:
2.5W max.
Relay status will change when
Supply Range: 9 to 30 VDC,
proper setpoint/process condition
inverter isolated
exists for 100msec
In-rush Current: 300mA, max.
Normal Mode (analog filtering):
Relay Contacts
<250msec, (10-90%)
2 SPDT (2 Form C) Relays
Setpoint
1 Relay per setpoint
Effectivity: Setpoint(s) are adjustable
Current Rating (resistive)
over 100% of the selected input
120VAC: 5A
span
240VAC: 2A
Repeatability (constant temp.):
28VDC: 5A
0.2% for temp > 0°C
0.3% for temp < 0°C
OMEGA ENGINEERING, INC. warrants this unit to be free of manufacturing defects for the life of the product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA's Customer Service Department will issue an Authorized Return (AR) number
OMEGAnet
SM
On-Line Service
Internet e-mail
immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. OMEGA's
http://www.omega.com
info@omega.com
WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design
limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged
as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA's
Servicing North America:
control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
USA:
One Omega Drive, Box 4047
ISO 9001 Certified
Stamford, CT 06907-0047
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
Telephone: (203) 359-1660
Fax: (203) 359-7700
damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by
e-mail:info@omega.com
it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
Canada:
976 Bergar
ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order,
Laval (Quebec) H7L 5A1
whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no
Telephone: (514) 856-6928
Fax: (514) 856-6886
e-mail: canada@omega.com
event shall OMEGA be liable for consequential, incidental or special damages.
For immediate technical sevice or application assistance:
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a "Basic Component" under 10 CFR 21 (NRC), used in or with any nuclear
installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
USA and Canada:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and additionally, purchaser will
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
SM
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Mexico and
Tel: (95) 800-TC-OMEGA
SM
Fax: (95) 203-359-7807
Latin America:
En Espanol: (203) 359-1660 ext. 2203
e-mail: espanol@omega.com
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
Tel: (31) 20 6418405
Fax: (31) 20 6434643
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER
Toll Free in Benelux: 06 0993344
MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA'S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
e-mail: nl@omega.com
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
Czech Republic:
Ostravska 767, 733 01 Karvina
Tel: 42 (69) 6311899
Fax: 42 (69) 6311114
FOR WARRANTY RETURNS, please have the following information
e-mail: czech@omega.com
available BEFORE contacting OMEGA:
1.
P.O. number under which the product was PURCHASED,
France:
9, rue Denis Papin, 78190 Trappes
2.
Model and serial number of the product under warranty, and
Tel:33 0130-621-400
Fax: 33 0130-699-120
3.
Repair instructions and/or specific problems relative to the product
Toll Free in France: 05-4-06342
e-mail: france@omega.com
Germany/Austria:
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
OMEGA's policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and
Tel:49 (07056) 3017
Fax: 49 (07056) 8540
engineering.
Toll Free in Germany: 0130 11 21 66
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
ã Copyright 1996 OMEGA ENGINEERING, INC. All rights reserved. This documentation may not be copied, photocopied, reproduced, translated, or reduced to any
e-mail: germany@omega.com
electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.
United Kingdom:
25 Swannington Road,
P.O. Box 7, Omega Drive
ISO 9002 Certified
Broughton Astely, Leicestershire,
Irlam, Manchester,
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European
LE9 6TU, England
M44 5EX, England
New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
Tel: 44 (1455) 285520
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter
Tel: 44 (161) 777-6611
specifications without notice.
Fax: 44 (1455) 283912
Fax: 44 (161) 777-6622
WARNING: These product are not designed for use in, and should not be used for, patient connected applications.
Toll Free in England: 0800-488-488
e-mail: uk@omega.com
Material: Silver-Cadmium Oxide
5
Electrical Life: 10
operations at
rated load
Note: External relay contact
protection is required for use
with inductive loads (see relay
protection Figures 2 & 3).
Mechanical Life: 10
7
operations
Wire Termination
Screw terminations for 12-22 AWG
Agency Approvals
CSA certified per standard C22.2,
No. 0-M91 and 142-M1987 (File
No. LR42272) UL recognized per
standard UL508 (File No.E99775)
CE Conformance per EMC directive
89/336/EEC and Low Voltage 73/23/
EEC
Mounting
32mm and 35mm DIN Rail
PIN CONNECTIONS
11 N.O. Relay B
12 Com. Relay B
13 N.C. Relay B
21 DC Power (+)
22 DC Power (-)
23
No Connection
41 T/C Input (+)
42 T/C Input (-)
43 No Connection
51 N.O. Relay A
52 Com. Relay A
53 N.C. Relay A
WARRANTY/DISCLAIMER
RETURN REQUEST/ INQUIRIES
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair
charges. Have the following information available BEFORE contacting OMEGA:
1.
P.O. number to cover the COST of the repair,
2.
Model and serial number of product, and
3.
Repair instructions and/or specific problems relative to the product.
721-0609-00A
8/96
DRG-AR-TC
Field Configurable Limit Alarm
Instruction Sheet M2398/0796
DESCRIPTION
OPERATION
The DRG-AR-TC is a DIN rail mount,
The field configurable DRG-AR-TC
thermocouple input limit alarm with
limit alarm setpoints can be config-
dual setpoints and two contact closure
ured for HI or LO, failsafe or non-
outputs. The field configurable input
failsafe operation.
and alarm functions offer flexible
setpoints has a respective HI or LO
setpoint capability. There are up to six
deadband. In a tripped condition, the
temperature ranges available for each
setpoint is exceeded and the appro-
thermocouple type to ensure accura-
priate red LED will illuminate. The trip
cy and maximize setpoint resolution.
will reset only when the process falls
A bipolar input switch is provided for
below the HI deadband or rises above
temperature ranges below 0°C.
the low deadband (see Figure 1). For
proper deadband operation, the HI
The DRG-AR-TC is configurable as a
setpoint must always be set above the
single or dual setpoint alarm, with HI or
LO setpoint.
LO trips, upscale or downscale ther-
mocouple burnout detection and
In failsafe operation, the relay is en-
failsafe or non-failsafe operation. Also
ergized when the process is below the
included are adjustable deadbands
HI setpoint or above the LO setpoint
(0.25 to 5% of full scale input) for each
(opposite for non-failsafe). In the
setpoint and a flexible DC power sup-
failsafe mode, a power failure results
ply which accepts any voltage be-
in an alarm state output.
tween 9 and 30VDC.
Illustrating LO Setpoint
Illustrating HI Setpoint
DIAGNOSTIC LEDS
Setpoint
100
The DRG-AR-TC is equipped with
three front panel LEDs. The first is a
dual function LED labeled INPUT.
This green LED indicates DC power
50
and input signal status. Active DC
Relay Trips
power is indicated by an illuminated
(LED Red)
Relay returns to its
untripped condition
LED. If this LED is off, check line
Time
power and wiring connection. If the
Figure 1: Limit alarm operation and
input signal is more than 110% of the
effect of deadband(s).
full scale range, the LED will flash at 8
Hz. Below 0%, the flash rate is 4 Hz.
DYNAMIC DEADBAND
LSI circuitry in the DRG-AR-TC pre-
Two red LED's indicate the relay state
vents false trips by repeatedly sam-
for each setpoint. An illuminated red
pling the input. The input must remain
LED indicates the tripped condition.
beyond the setpoint for 100 millisec-
OUTPUT
onds, uninterrupted, to qualify as a
The DRG-AR-TC is equipped with two
valid trip condition. Likewise, the input
SPDT (form C) relays, rated at
must fall outside the deadband and
120VAC or 28VDC at 5 amperes.
remain there for 100 milliseconds to
Each of these relays is independently
return the alarm to an untripped con-
controlled by the field configurable set
dition. This effectively results in a
point and deadband.
"dynamic deadband" —based on
time— in addition to the normal
deadband.
CONFIGURATION
Unless otherwise specified, the
factory presets Model DRG-AR-TC as
follows:
Each of the
Input:
J Type
Range:
0 to 350°C
Output:
Dual, SPDT
Trip:
A: HI, B: LO
Failsafe:
No
Deadband:
A, B: 0.25%
The DC power input accepts any DC
source between 9 and 30V, typically
a 12V or 24VDC source is used.
For other I/O ranges, refer to
Table 1 and reconfigure switches SW1
and SW2 for the desired input type,
range and function.
WARNING: Do not attempt to change any
switch settings with power applied. Severe
damage will result!
1. With DC power off, position switch
SW1-1, 2, 3 and SW2-
Relay returns to its
untripped condition
1 through 6 for the desired input range
Relay Trips
(LED Off)
(LED Red)
(Table 1).
} 10% Deadband
2. Set positions 4 and 5 of function
} 10% Deadband
switch "SW1" to ON for a HI trip
setpoint or OFF for a LO trip setpoint
(LED off)
(Figure 4).
3. Set position 6 of function switch
"SW1" to ON for non-failsafe opera-
tion or OFF for failsafe operation (e.g.
alarm trips upon power failure).
4. Set positions 7 and 8 of function
switch "SW1" to upscale or downscale
burn-out.

Advertisement

loading

Summary of Contents for Omega DRG-AR-TC

  • Page 1 For immediate technical sevice or application assistance: CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a "Basic Component" under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,...
  • Page 2 CALIBRATION Table 1: DRG-AR-TC Input Range Selector -Switch Settings 1. After configuring the DIP switches, connect the input to a calibrated TC source and apply power. Refer to the terminal wiring (Figure 5). NOTE: to maximize thermal stability, final calibration should be performed in the...