Way Air Flow System - Mitsubishi SLZ-KA25VA Technical & Service Manual

Hide thumbs Also See for SLZ-KA25VA:
Table of Contents

Advertisement

7

4-WAY AIR FLOW SYSTEM

7-1. Fresh air intake (Location for installation)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Fresh air intake
Refrigerant pipe
7-2. Fresh air intake amount & static pressure characteristics
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
Taking air into the unit
Static pressure : P [Pa]
50
0.5
1.0 1.5 2.0 2.5 3.0 3.5
0
-50
-100
-150
-200
-250
-300
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
7-3. Interlocking operation method with duct fan (Booster fan)
Whenever the indoor unit is operating,
the duct fun
operates.
(1)Connect the optional multiple remote
controller
adapter(PAC-SA88HA-
E)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow
and Orange connector lines.
Use a relay under 1W.
MB: Electromagnetic switch power
relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
Drain pipe
Electrical Box
3
Air flow : Q [m
/min]
CN51
on
indoor unit
board
Multiple remote
controller adapter
PAC-SA88HA-E
CN51
19
Detail drawing of fresh air intake
[100
25
[73.4
3-[2.8 hole
Cut out hole
Burring hole
Ceiling surface
How to read curves
Duct characteristics
Curve in the
at site
1
left praphs.
0
Q
2
Q
3
Q
Qa
Be sure to secure insulation
material by tape and such
Green
5
Yellow
Orange
1
Connector (5P)
Red
Brown
Package side
Multiplr remote
controller adapter
PAC-SA88HA-E
Indoor controller board
CN51(WHT)
Q ... Planned amount of fresh air intake
<m
3
A ... Static pressure loss of fresh air
intake duct system with air flow
amount Q
B ... Forced static pressure at air condi-
tioner inlet with air flow amount Q
C ... Static pressure of booster fan with
air flow amount Q
D ... Static
pressure
loss
increase
amount of fresh air intake dust sys-
tem for air flow amount Q <Pa>
E ... Static pressure of indoor unit with air
flow amount Q
Qa ... Estimated amount of fresh air
intake with out D
<m
/min>
3
~
MB
Installation at site
Be sure to secure insulation
material by tape and such
Distance between indoor
controller board and relay
must be within 10m.
/min>
<Pa>
<Pa>
<Pa>
<Pa>