Samsung AC024JXADCHA Installation Manual page 15

Table of Contents

Advertisement

Connecting the cable
Power Cable Specifications
f The power cable is not supplied with air conditioner .
f
- Select the power supply cable in accordance with relevant local and national regulations .
- Wire size must comply with the applicable local and national code .
- Specifications for local wiring power cord and branch wiring are in compliance with local cord .
Model
AC018JXADCHA
1 . RLA is based on AHRI 210/240 colling standard condition [Indoor temp . : 26 . 7 °C / 80 °F(DB) / 19 . 4 6 °C /
67 °F(WB), Outdoor temp . : 35 °C / 95 °F(DB)]
NOTE
2 . Voltage tolerance is ± 10 % .
3 . Maxium allowable voltage between phases is 2 % .
Symbols
• RLA : Rated Load Ampere
• FLA : Full Load Ampere
• MCA : Minumum Circuit Ampere (A)
• MOP : Maximum Overcurrent Protective Device (A)
Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
Power supply
1Φ, 208~230V, 60Hz
f Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
f
cord . (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
1-phase terminal block spec
AC power : M4 screw
1(L) 2(N)
L
11 . 4
10 . 1
L1
L2
POWER
14
4way Outdoor_북미향_IM_EN_05138A-00.indd 14
Power source
RLA
208~230V/60Hz
6 . 1 0 A
Power supply
Max/Min(V)
±10%
When installing the indoor unit in a computer room or net work room, use the
double shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R
type .
Communication : M4 screw
N
11 . 4
FLA
0 . 1 3
Indoor Power Cable
0 . 0 039 in² , 3wires
10 . 1
MCA
MOP
14 . 5 A
20 A
Communation Cable
0 . 0 011~0 . 0 023 in², 2wires
2014-12-08 오후 3:12:46

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac030jxadchaAc036jxadchaAc042jxadchaAc048jxadcha