9.3.1.17. Anti-Freezing Control
1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase +20 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
9.3.1.18. Anti-Dew Formation Control
Spray protection Control
• • • • In the case of indoor form ceiling floor, duct and mini-cassette.
a. Purpose
To prevent dew.
b. Control start conditions
When indoor units are ceiling floor, duct and mini-cassette.
c. Control contents
Hz control is carried out according to the spray prevention status transmitted from indoor.
Spray prevention
status (transmitted indoor)
0 (it usually controls)
1 (rise)
2 (changeless)
3 (down)
Change is once to 10 seconds.
* Once the stand-up went into the down domain by Fcmax as for the Fcmax domain, it shifts to relative changes control domain.
When the higher rank of relative control has this control and the status signal od 2-3 has come out.
Relative change control is stopped and follows directions of spray control.
Priority is given to the which is larger when freeze prevention down status and spray prevention down status are transmitted
simultaneously.
In the case of spray status
Relative control domain
Usually, control
Relative change control priority
Changeless
-2 Hz/10 seconds
0, it is referred to as maxFc.
CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
Control contents
Usually, control
On tap up/10 seconds
Changeless
-2 Hz/10 seconds
73
MAX domain