1.3.3 Performance Requirements

1.3.3.1 AC Input to UPS
A. Voltage: The point at which the UPS transfers to battery operation shall be dependent on the amount of load
that the UPS is supporting. The UPS shall operate from the following voltage ranges without drawing power
from the batteries:
Low Line Voltage Range
Low Line Voltage
100% to 91%
90% to 71%
70% to 31%
30% to 0%
High Line Voltage Range
High Line Voltage
High Line Transfer
High Line Comeback
B. Frequency: The UPS shall auto-sense input frequency of 50Hz or 60Hz when first powered up and shall use
this frequency as the default output frequency. Once started the input frequency operating window shall be
40-70Hz without going to batteries. The UPS shall be capable of cold start with a default output frequency of
60Hz.
C. Input Power Factor: >0.99 lagging at rated load.
D. Input Current reflected distortion: 5% THD maximum at rated load.
E. Input Current Ratings:
UPS Model #
GXT3-5000RT208
GXT3-6000RT208
F. Surge Protection: The UPS shall utilize metal oxide varistors (MOVs) rated at 175V, 150 Joules minimum
connected L1-N and L2-N; 300V, 150 Joules minimum connected L1-G, L2-G and N-G.
SL-23188_REV1_08-10
GXT3-5000RT208
L/L Transfer
88 ± 3.1VAC
L/L Comeback
95 ± 3.1VAC
L/L Transfer
84 ± 3.1VAC
L/L Comeback
91 ± 3.1VAC
L/L Transfer
70 ± 3.1VAC
L/L Comeback
77 ± 3.1VAC
L/L Transfer
60 ± 3.1VAC
L/L Comeback
67 ± 3.1VAC
208V Models
139.5 ± 3.1VAC
132.5 ± 3.1VAC
VA
Watt
Hz
5000
4000
50/60
5000
4000
50/60
5000
4000
50/60
4500
3600
50/60
4000
3200
50/60
6000
4800
50/60
5600
4800
50/60
6000
4800
50/60
5400
4320
50/60
3840
4800
50/60
GXT3-6000RT208
98 ± 3.1VAC
105 ± 3.1VAC
88 ± 3.1VAC
95 ± 3.1VAC
74 ± 3.1VAC
81 ± 3.1VAC
60 ± 3.1VAC
67 ± 3.1VAC
VAC
L1
L2
120/240
10.4
10.4
115/230
10.85
10.85
120/208
10.4
10.4
110/220
10.25
10.25
100/200
10
10
120/240
12.5
12.5
115/230
12.15
12.15
120/208
12.5
12.5
110/220
12.25
12.25
100/200
12
12
4
Liebert GXT3-5000/6000RT208
Total Amps
20.8
21.7
20.8
20.5
20
25
24.3
25
24.5
24
Guide Specifications