Fault messages on the display
Displayed
System characteris-
fault code
tics
F2
Burner in a fault
state
F3
Burner in a fault
state
F4
Burner in a fault
state
F8
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner blocked
(cont.)
Cause
The temperature
limiter has respon-
ded
Flame signal is
already present at
burner start
No flame signal
Fuel valve closes
too late
Fan speed too low
during burner start
Fan not at stand-
still
Electrical fan con-
trol (control unit)
faulty
Troubleshooting
Measures
Check heating system fill
level. Check circulation
pump. Vent the system.
Check the temperature
limiter and connecting
leads (see page 48).
Press "Reset" (see
page 42).
Check ionisation elec-
trode and connecting
cables.
Press "Reset" (see
page 42).
Check the ignition/ionisa-
tion electrode and con-
necting cables, check the
gas pressure, check the
gas train, ignition and con-
densate drain.
Press "Reset" (see
page 42).
Check gas train. Check
both control paths.
Press "Reset" (see
page 42).
Check fan, fan connecting
cables and power supply;
check fan control.
Press "Reset" (see
page 42).
Check fan, fan connecting
cables and fan control.
Press "Reset" (see
page 42).
Check fan connecting
cable; if required, replace
or replace control unit.