Pressure, diff. (switching difference)
Circuit
1
Setting of the switching difference for measured static pressure (pressure
transmitter). The difference is symmetrical around the 'Pressure des. ' See
also 'Pressure des. '
P exercise (pump exercise)
Circuit
1
The time the pump is activated during exercise. Exercise takes place every
day (at 12:00).
OFF:
No pump exercise.
1 ... 200: Activation time during exercise.
Valve delay
Circuit
1
Setting of the time for activation of the ON/OFF valve after start of the refill
water pump.
No. of pumps
Circuit
1
Setting of the number of pumps in the refill water circuit.
OFF:
The refill water pump function is controlled by the
master controller.
1 ... 2:
The refill water function has one or two pumps.
76
DEN-SMT/DK
ECL Comfort 210 / 310, application A231 / A331
11322
Setting range
Factory setting
0.1 ... 5.0 bar
1.5 bar
11320
Setting range
Factory setting
OFF / 1 ... 200 s
11325
Setting range
Factory setting
0 ... 30 s
11326
Setting range
Factory setting
OFF / 1 ... 2
The settings in 'Pressure, des.' and 'Pressure, diff.' have no influence
when a pressure switch is used.
OFF
Refill pump
ON
OFF
1 s
ON
Refill valve
OFF
1
Refill water
pump
When selecting OFF and a demand for refill occurs, the controller
for the actual circuit sends the requirement via the ECL 485
communication bus to the master controller.
The master must be running an application with refill water function.
The master starts the refill water pump and sends, via the ECL 485
communication bus, a message that the refill water pump is started.
The refill water valve then opens.
The slave must have an address 1 ... 9.
VI.LG.P1.02
'Valve delay'
ECL 485
communication
bus
Refill water
valve
Danfoss District Energy
Time