Download Print this page

Installation Instructions; How To Order - Murphy PSB Owner's Manual

Direct mount pressure switch

Advertisement

Dimensions
2-1/4 in.
(57 mm)
NO C NC
Slot head terminal
screws (4-40, UNC-2A)
Trip Point Chart
Factory setting *
Ranges available
psi (kPa/MPa) [bar]
psi (kPa) [bar] Falling
0-15 (0-103) [0-1.03]
3 (21) [.21]
0-30 (0-207) [0-2.07]
7 (48) [.48]
0-50 (0-345) [0-3.45]
10 (69) [.69]
0-75 (0-517) [0-5.17]
15 (103) [1.03]
0-100 (0-689) [0-6.89]
20 (138) [1.38]
0-150 (0-1.03) [0-10.34] 30 (207) [2.07]
0-200 (0-1.38) [0-13.79] 50 (345) [3.45]
0-300 (0-2.07) [0-20.70] 75 (517) [5.17]
0-400 (0-2.76) [0-27.60] 150 (1.03) [10.34]
* These points will be used if switch trip point is not specified.

How to Order

To order the PSB model use the diagram below.
PSB –
Pressure Range
Specify maximum value
from chart above.
Switch Trip Point
F = Factory set to trip on falling. Specify "F" and the set point value.
Example: PSB-100-F20.
R = Factory set to trip on rising, Specify "R" and the set point value.
For units of measure other than psi, specify the set point value
followed by unit of measure as follows:
B = Bar
K = kPa/MPa
M = kg/cm2
Example: PSB-7B-2B
† Switch set point value will be stated on label.
www.fwmurphy.com
918.317.4100 Email: sales@fwmurphy.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
2-9/16 in.
(65 mm)
1/8-27 NPT
2-1/32 in. Dia.
(52 mm)
1/2 in. (13 mm)
Square wrench flats
Maximum pressure
psi (kPa) [bar]
30 (207) [2.07]
60 (414) [4.14]
100 (0-689) [0-6.89]
150 (0-1.03) [0-10.34]
200 (0-1.38) [0-13.79]
300 (0-2.07) [0-20.70]
400 (0-2.76) [0-27.60]
500 (3.45) [34.50]
500 (3.45) [34.50]
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our
specifications and designs at any time. MURPHY, the Murphy logo are registered and/or common law
trademarks of Murphy Industries, Inc. This document, including textual matter and illustrations, is copyright
protected by Murphy Industries, Inc., with all rights reserved. (c) 2006 Murphy Industries, Inc.
PSB-9104B page 2 of 2

Installation Instructions

Mounting
CAUTION: Use wrench on shank to tighten or loosen pressure
connection. DO NOT TWIST CASE, which will damage the unit and
void the warranty.
1. Before installing the PSB switch, apply sealant, such as Teflon tape,
to the threads (be sure sealant does not block the inlet orifice).
2. The PSB can be mounted in horizontal or vertical angles (do not
mount switch facing down).
3. Locate the unit in place and secure it by tightening
the 1/8-27 NPT fitting into the desired location (do not
overtighten). DO NOT TWIST CASE.
Wiring
CAUTION: DISCONNECT Electrical power before wiring.
1. Switch contacts (below) are shown
with no pressure applied to the
PSB switch.
2. A spade (forked) terminal
is recommended for all
PSB switch connections.
3. Complete the wiring operation
making sure the voltage and
current requirements are within
the PSB switch electrical
rating (see the typical wiring
diagram at right).
WRONG
UP
Normally
Closed (N.C.)
Common (C)
Normally
Open (N.O.)
Printed in U.S.A. 0591124M