9-4-1. Static Pressure Characteristics of Each Model
Fig. 9-4-1 RAS-M10GDCV-E, RAS-M10GDV-E
80
70
60
Upper limit of
external static
pressure
Air volume limit
50
(Min.)
380m³/hr.
40
30
20
Low tap
10
Air volume limit
(Max.)
720m³/hr.
0
200
300
400
500
Air volume (m³/hr.)
Fig. 9-4-2 RAS-M13GDCV-E, RAS-M13GDV-E
80
70
60
Upper limit of
external static
pressure
Air volume limit
50
(Min.)
410m³/hr.
40
30
20
Low tap
10
0
200
300
400
500
Air volume (m³/hr.)
8
7
6
5
High tap
4
3
2
Lower limit of
external static
pressure
1
0
600
700
800
900
8
7
6
High tap
5
4
3
Lower limit of
2
external static
pressure
1
Air volume limit
(Max.)
780m³/hr.
0
600
700
800
900
www.ilmalämpöpumput.com
Fig. 9-4-3 RAS-M16GDCV-E, RAS-M16GDV-E
80
70
60
50
Air volume limit
(Min.)
430m³/hr.
40
30
20
Low tap
10
0
200
300
400
Model RAS-
Air
Max.
volume
capacity
point
Static
pressure
Air
volume
Max. air
volume
Static
pressure
Air
Min.
volume
capacity
point
Static
pressure
Air
volume
Min. air
volume
Static
pressure
Unit for static pressure : Pa (mmAq)
– 28 –
Upper limit of
external static
High tap
pressure
Lower limit of
external static
pressure
Air volume limit
(Max.)
780m³/hr.
500
600
700
800
Air volume (m³/hr.)
M10GDCV-E M13GDCV-E M16GDCV-E
M10GDV-E
M13GDV-E
M16GDV-E
650
700
54.9
63.7
(5.6)
(6.5)
720
780
35.3
41.2
(3.6)
(4.2)
400
430
10.8
12.7
(1.1)
(1.3)
380
410
18.6
21.6
(1.9)
(2.2)
Unit for air volume : m³/hr.
8
7
6
5
4
3
2
1
0
900
700
63.7
(6.5)
780
41.2
(4.2)
450
13.7
(1.4)
430
23.5
(2.4)