UTICA BOILERS MGB50 Installation, Operation & Maintenance Manual page 8

Mgb series cast iron gas fired boilers for forced hot water
Table of Contents

Advertisement

Figure 6 - Bypass Piping Automatic Mixing Valve
Figure 7 - Bypass Piping - Fixed Low Temp Only Automatic Mixing Valve
7.
Installation using circulators and zone valves are
shown in Figures 8-11. For further piping information
refer to I=B=R Installation and Piping Guide.
WARNING
!
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
Install discharge piping from safety relief valve.
8.
Use ¾" or larger pipe.
Use pipe suitable for temperatures of 375°F (191°C)
or greater.
connectIng supply and return pIpIng
TO SYSTEM
WATER INLET
EXPANSION
TANK
CIRCULATOR
SHUT-OFF
VALVE
TO SYSTEM
SYSTEM
CIRCULATOR
WATER INLET
EXPANSION
CIRCULATOR
SHUT-OFF
VALVE
BOILER
PRESSURE
BALL VALVE
REDUCER VALVE
3 WAY MIXING
CHECK VALVE
VALVE
V1
V2
TANK
BOILER
PRESSURE
BALL VALVE
REDUCER VALVE
ZONE VALVE
CHECK VALVE
Individual boiler discharge piping shall be independent
of other discharge piping.
Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
Run pipe as short and straight as possible to location
protecting user from scalding and properly drain
piping.
Install union, if used, close to safety relief valve outlet.
Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
Terminate pipe with plain end (not threaded).
8
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
AIR SEPARATOR
HOSE BIB
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
AIR SEPARATOR