Tools Needed:
1.
Pitot Tube
2.
Incline Manometer/Magnahelic
Example 1:
Return ESP after Filter
Supply ESP before Coil
------------------------------------------------------
Total ESP
Example 2:
Return ESP before Filter
Filter Static Pressure Drop @ 2000 cfm 0.10 in.w.c.
Supply ESP after Coil
Coil Static Pressure Drop Wet
------------------------------------------------------
Total ESP
Both Examples 1 and 2 are correct. Example 1 ESP readings were taken as laid out in static pressure reading location diagrams (Figures 5 - 7).
Example 2 readings are taken as described. The coil and filter static pressure drops were taken from the manufacturer's product data sheets with the
assumption that 2000 cfm is being delivered.
Figure 7 – Horizontal Right Total Static Pressure Reading Locations
0.20 in.w.c.
0.40 in.w.c.
0.60 in.w.c.
0.10 in.w.c.
0.20 in.w.c.
0.20 in.w.c.
0.60 in.w.c.
- 42 -