3-7. Replace the Drain Hose

(1) Rear view for left piping installation
Drain hose
Drain cap
(3) How to pull the piping and drain hose out, in case of the embedded piping.
Apply putty or
caulking material
to seal the wall
opening
PVC tube for drain
hose (VP-20)
(4) In case of left piping how to insert the connection cable and drain hose.
Drain hose
Cable
Piping

3-8. Drain Hose Adapter (supplied) Usage

● Join indoor drain hose to 3/4" (20 mm) nominal PVC pipe size
by using drain hose adapter (supplied) when necessary.
NOT E
Make sure indoor unit drain hose & 3/4" (20 mm) nominal PVC
pipe are fully inserted to drain hose adapter (supplied).

3-9. Check the Drainage

● Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
● Pour a glass of water into the drain tray-styrofoam.
● Ensure that water flows out from drain hose of the indoor unit.
(2) Adjust the piping slightly downwards
Fig. 3-18
Connection cable
Connection cable
Piping
Drain hose from
main unit
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
(For the right piping,
follow the same procedure)
Fig. 3-23
Sleeve for
PIPE HOLE CENTER
piping hole
DISTANCE
TO PIPE
HOLE
CENTER
128 mm
Drain hose
Fig. 3-19
PVC tube for
drain hose
Fig. 3-21
11
More than 3.7 ft. (1150 mm)
Drain hose
Piping
Indoor unit
2-53/64" (72 mm)
NOT E
Attention not to bend up
drain hose
Indoor unit
drain hose
Close join by Vinyl Tape
(field supplied)
Drain hose adapter (supplied)
3/4" (20 mm) nominal PVC pipe
- Install incline downward more than 1°
- Apply PVC glue at the join.
Drain tray-styrofoam
Connection cable
Fig. 3-20
Cable
Piping
Fig. 3-22
Fig. 3-24
Fig. 3-25
Fig. 3-26