4-3 CONTROL KIT & wired remote controller errors
- If an error occurs, (
) icon will be displayed on the wired remote controller.
- Press the Test button to see the error code.
Display
101
CONTROL KIT / OUTDOOR UNIT wire connection error
162
EEPROM Error
198
Error of Terminal Block's Thermal Fuse(Open)
201
CONTROL KIT/OUTDOOR UNIT communication error (Matching error)
202
CONTROL KIT/OUTDOOR UNIT communication error (3 min)
203
Communication error between INVERTER and MAIN MICOM (6 min)
221
OUTDOOR UNIT temperature sensor error
231
condenser temperature sensor error
251
Discharge temperature sensor error
320
OLP sensor error
403
Detection of OUTDOOR UNIT compressor freezing (During cooling operation)
404
Protection of OUTDOOR UNIT when it is overload (during Safety Start, Normal operation state)
407
Comp down due to high pressure
416
Discharge of a compressor is overheated
425
Power source line missing error (only for 3-phase model)
440
Heating operation blocked (outdoor temperature over 35°C)
441
Cooling operation blocked (outdoor temperature under 9°C)
458
OUTDOOR UNIT fan1 error
461
[Inverter] Compressor startup error
462
[Inverter] Total current error/PFC over current error
463
OLP is overheated
464
[Inverter] IPM over current error
465
Compressor V limit error
466
DC LINK over/low voltage error
467
[Inverter] Compressor rotation error
468
[Inverter] Current sensor error
469
[Inverter] DC LINK voltage sensor error
470
EEPROM Read/Write error
471
[Inverter] OTP error
474
IPM(IGBT Module) or PFCM temperature sensor Error
475
OUTDOOR UNIT fan2 error
484
PFC Overload Error
485
Input current sensor error
500
IPM is overheated
554
Gas leak error
590
Inverter EEPROM Checksum error
601
Communication error between the CONTROL KIT and wired remote controller
602
Wired remote controller Master/Slave setting error
604
Communication tracking error between the CONTROL KIT and wired remote controller
607
Communication error between the Master and Salve wired remote controllers
901
Water inlet (PHE) temperature sensor error(open/short)
902
Water outlet (PHE) temperature sensor error(open/short)
903
Water outlet (backup heater) temperature sensor error.
904
DHW tank temperature sensor error
906
Outdoor Eva Inlet Temp Sensor (open/short)
Flow switch and water pump error (F/S signal is OFF for 10 sec. during the water pump signal is
911
ON)
Flow switch and water pump error (Water pump signal is OFF for 60sec during the F/S signal is
912
ON)
916
Mixing valve temp sensor (open/short)
When the product does not work during or after the concrete curing function and it displays "CC" on the wired remote controller, contact the installer to
cancel the concrete curing function.
NOTE
Samsung Electronics
Explanation
Error Source
CONTROL KIT, OUTDOOR UNIT
CONTROL KIT
CONTROL KIT
CONTROL KIT, OUTDOOR UNIT
CONTROL KIT, OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
Wired Remote Controller
Wired Remote Controller
CONTROL KIT, Wired Remote Controller
Wired Remote Controller
OUTDOOR UNIT
OUTDOOR UNIT
CONTROL KIT
CONTROL KIT
OUTDOOR UNIT
CONTROL KIT
CONTROL KIT
CONTROL KIT
57