VENTILATION

When installing the heater indoors, it is imperative that an adequate supply of fresh air is provided
for combustion. Failure to provide adequate ventilation voids all warranties and may be a danger
to persons or property.
Two permanent openings shall be provided directly to outside. The openings shall be located to
ensure the distance between the top of the upper opening and the ceiling of the room or enclosure,
and the distance between the bottom of the lower opening and the floor of the room or enclosure
does not exceed 5% of the height of the room or enclosure.
The minimum vertical dimension of any free ventilation opening shall be 6 mm.
The minimum free ventilation area provided by each opening shall be:
The following diagram is provided as a guide only. All flueing and installation work must be
carried out by an authorized person. Flueing must conform to local regulations and to A.G.A.
installation code AS5601. Care must be taken to provide the correct ventilation and correct flueing
materials in close proximity to combustible surfaces.
1500
Bolted
sleeve to
connect flue
Draft diverter
purchased
from Hurlcon
An indoor draught diverter must be purchased from Hurlcon and fitted to unit in accordance
with AstralPool's instructions and Installation Codes before the heater can be enclosed.
MX Pool and Spa Heater
MODEL
AREA
MX 125
35,000 mm
MX 150
50,000 mm
MX 200
65,000 mm
MX 250
80,000 mm
MX 300
100,000 mm
MX 400
130,000 mm
MX 500
160,000 mm
Approved gas
termination cowl
2
2
2
2
2
2
2
Upper grille for fresh
air ventilation
Lower grille for fresh
air ventilation
Page 11