▼ To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each unit within
the same refrigerant system.
* Change the address in the address check / change mode.
[Procedure] (Operation while the air conditioner stops)
1
TEST
Push the timer time
+
buttons simultaneously for 4 seconds or more.
Firstly, the line 1, CODE No.
(Address Change) is displayed.
2
SWING/FIX
Using
/
buttons, select the line address.
3
SET
Push
button.
• The indoor address, which is connected to the refrigerant system of the selected header unit is displayed
and the fan is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
4
The indoor address of the setup data moves up/down by the timer time
Change the setup data to a new address.
5
SET
Push
button to determine the setup data.
6
Every pushing
button, the indoor unit numbers in the same refrigerant line are
successively displayed. Only fan of the selected indoor unit operates.
4
6
Repeat the procedure
to
and change all the indoor addresses so that they are not duplicated.
7
SET
Push
button.
(All the displays on LCD go on.)
8
Push
TEST
button to finish the procedure.
CODE No.
SET DATA
SETTING
UNIT No.
R.C
No.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
1
TIME
SAVE
VENT
FILTER
RESET TEST
SET
CL
SWING/FIX
UNIT LOUVER
3
Deletion of line selection
Here, if the unit No. is not called up, the
header unit in this system does not exist.
CL
Push
button, and then select a line
2
according to procedure
.
41-EN
/
buttons.
CODE No.
SET DATA
SETTING
UNIT No.
R.C
No.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
4
TIME
SAVE
VENT
FILTER
RESET TEST
SET
CL
SWING/FIX
UNIT LOUVER
8
2
5, 7
To finish the set
Operation procedure
1
2
3
4
5
6
7
– 21 –
Clearance of address
(Return to status (Address undecided) factory default)
Method 1
An address is individually cleared from a wired remote controller.
"0099" is set up to line address, indoor address, and group address data from the wired remote controller.
(For the setup procedure, refer to the above-mentioned address setup from the wired remote controller.)
Method 2
Clear the indoor addresses in the same refrigerant system from the outdoor unit.
1
Turn off the power of the refrigerant system to be returned to the status factory default, and
change the outdoor unit to the following status.
1) Remove the relay connector between [U1U2] and [U3U4].
(If it has been already removed, leave it as it is.)
2) Turn on SW30-2 on the interface P.C. board of the outdoor unit if it is ON.
(If it has been already ON, leave it as it is.)
U3 U4
U1 U2
U1 U2
A B
Remote
controller
2
Turn on the indoor / outdoor power of which address is to be cleared. After approx. 1 minute,
check that "U.1. - - -" is displayed, and then execute the following operation on the interface P.C.
board of the outdoor unit of which address is to be cleared in the refrigerant system.
SW01
SW02
SW03
2
1
2
2
2
2
3
6
After "A.d. c.L." has been displayed on 7-degment display, return SW01 / SW02 / SW03 to 1/1/1.
4
When the address clearing has correctly finished, "U.1.L08" is displayed on 7-degment display
after a while.
If "A.d. n.G." is displayed on 7-degment display, there is a possibility which is connected with the other
refrigerant system. Check again the relay connector between [U1U2] and [U3U4] terminals.
8
End
NOTE
Be careful that the other refrigerant system address may be also cleared if clearing operation is not correctly executed.
5
After clearing of the address, set up an address again.
Center unit
Center unit
U3 U4
Outdoor unit
Outdoor unit
U1 U2
U1 U2
U1 U2
U1 U2
A B
A B
A B
Remote
Remote
controller
controller
Unit of which address is to be returned to the initial status
SW04
After checking that "A.d.buS" is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
After checking that "A.d.nEt" is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
Central control
device
U1
U2
U3
U4
U3 U4
Outdoor unit
U1 U2
U1 U2
A B
Remote
controller
Address which can be cleared
Line + Indoor + Group address
Central address
42-EN