Self-Diagnosis Function - LG AS-W1863 Series Svc Manual

Universal air conditioner
Table of Contents

Advertisement

Troubleshooting Guide

Self-diagnosis function

1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
The cause of malfunction
Code
Indoor TH. is short or open.
1
Outdoor TH. is short or open.
2
Temp. of Heat sink is over 95°C.
4
/Heat sink TH. is short or open.
Comunication error (serial
5
comunication).
DC peak error.
6
Running current is over-
7
loaded. (CT2)
Indoor fan lock error
8
(BLDC fan model)
Outdoor fan lock error
9
(BLDC fan model)
D-PIPE TH is short or open.
10
❈ Error code ➅, ➆ can't be operated unless the power cord is removed.
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB ass'y)
Error
The cause of malfunction
Code
Indoor TH. is short or open.
2
Temp. of Heat sink is over 95°C,
4
or Heat sink TH. is shortor open.
Comunication error (serial
5
comunication).
DC peak error.
6
Running current is over-
7
loaded.
Outdoor fan lock error
9
(BLDC fan model)
D-PIPE TH is short or open.
10
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Malfunction indicator
The display show "C1"
The display show "C2"
The display show "C4"
The display show "C5"
The display show "C6"
The display show "C7"
The display show "C8"
The display show "C9"
The display show "CA"
Malfunction indicator
The LED01M will be blinking
twice.
The LED01M will be blinking 4
times.
The LED01M will be blinking 5
times.
The LED01M will be blinking 6
times.
The LED01M will be blinking 7
times.
The LED01M will be blinking 9
times.
The LED01M will be blinking 10
times.
- 66 -
The operating state
Keep operating state.
Keep operating state.
Restart compressor when Heat sink
Temp is 85°C below.
The operation is off(enable to restart
by remote controller).
Compressor will be turned off immediately.
(not enable to restart by remote controller)
Compressor will be turned off immediately.
(not enable to restart by remote controller)
The operation is off(enable to restart
by remote controller).
The operation is off(enable to restart
by remote controller).
Compressor will be turned off immediately.
(restart compressor when D-PIPE TH. is
recovred)
The operating state
Keep operating state.
Restart compressor when heat sink
Temp. is 85°C below.
The operation is off(enable to restart
by remote controller).
Compressor will be turned off immediately.
(not enable to restart by remote controller)
Compressor will be turned off immediately.
(not enable to restart by remote controller)
The operation is off(enable to restart
by remote controller).
Compressor will be turned off immediately.
(restart compressor when D-PIPE TH. is
recovered)
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As-w2463 series

Table of Contents