Flue System - Ferroli F 30 B Instructions For Use, Installation And Maintenance

Wall-mounted gas fired, condensing combination boiler
Table of Contents

Advertisement

Ferroli F 30 B
Follow the instructions A given in fig. 8a to access the electrical connection terminal block (B fig. 8b). The layout of
the terminals for the various connections is given in the wiring diagram in the Technical Data chapter.
A
Room thermostat
CAUTION: THE ROOM THERMOSTAT MUST HAVE VOLTAGE FREE CONTACTS. CONNECTING
230 V. TO THE TERMINALS OF THE TIME CLOCK AND ROOM THERMOSTAT WILL IRREPARABLY
DAMAGE THE P.C.B.
When connecting a room thermostat with a daily or weekly program, or a timer switch, do not
take the power supply for these devices from their cut-out contacts. Their power supply must
be taken with a direct connection to the mains or with batteries, depending on the type of
device (isolation to mains fed clocks via a 3amp fused spur).

2.6 Flue system

The unit is "type C" with a sealed chamber and forced draught, the air inlet and flue outlet
must be connected to one of the following flue systems. With the aid of the tables and methods
of calculation indicated, before commencing installation, it is first necessary to check that the
flue system does not exceed the maximum permissible length. The current standards and local
regulations must be observed.
It should be noted that only Ferroli flue system and accessories should be used on this appliance, as per BS
5440 2000 and C.E. test certification.
fig. 8a
B
fig. 8b
15