Alignment And Adjustments; P(External Static Pressure) Setting For Phase Control Motor - Samsung DC42GTVA Service Manual

Table of Contents

Advertisement

3. Alignment and Adjustments

3-1 E. S. P(External Static Pressure) Setting for Phase Control Motor
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation
condition. If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that the duct
becomes shorter, adjust the fan speed by referring the following table. Refer to the page 3-1 to set the option code.
Static Pressure(mmAq)
CMM
Model
Step
(CFM)
38(1341)
Hi
Mid
34(1200)
DH140EAMC
Low
29.5(1041)
Hi
29.5(1041)
DH105EAMC
Mid
27(953)
Low
24(847)
Note : •
represents E. S. P(External Static Pressure) range of factory setting.
You don't have to adjust the fan speed separately if the external static pressure of the installation place is in
When it is out of
• If you input the inappropriate option code, error may occur or the air conditioner is out of order. The option code must be
inputted correctly by the installation specialist or service agent.
Option items
Remote
Control
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Model
DH140EAMC
DH105EAMC
3-1
0
2
015813
015814
-13018E
-1300A0
015814
015814
-100091
-1000A2
, input the appropriate option code.
4
6
Option Code for Indoor Unit
015814
015814
-1300C2
-1300E5
015814
015814
-1000C3
-1000E5
8
10
015814
015814
-130217
-130249
015814
015814
-100247
-1002FC
Samsung Electronics
15
015814
-1303E1
-
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dc48gtvaUh105gamcDh105eamcUh105eamcDh140eamcUh140gamc

Table of Contents