AVENAR detector 4000
The first digit of the 8-digit serial number represents the year of manufacturing.
Optical system value:
Optical system value (display of the current contamination value)
0 ... 170
0 ... 350
350 ... 450
450 ... 510
>511
Temperature value:
Temperature value [°C] (display of the value currently being measured by the thermal
sensor):
FAH-425-T-R, FAP-425-OT-R, FAP-425-OT,
FAP-425-DOT-R
FAP-425-DOTC-R
CO value:
Display of the value currently being measured by the CO sensor
The CO value specifies the currently-measured CO concentration. The specified number is
calculated as the difference between the current measurement value and the stand-by value
stored in the detector. The CO concentration displayed lies in the range between 0 (normal
operating condition) and 555 (max. measurement value of the sensor).
EMC value:
Indicates EMC level. There is a current EMC value (short-term measurement) used during/right
after installation of the detector and average EMC value (long-term measurement) used during
operation of the detector.
Current EMC value
0...8
9...20
>20
Operating hours starting from the initial start-up of the detector.
Bosch Sicherheitssysteme GmbH
Current analog values
Average EMC value
0...49
50...79
80...100
Operating hours counter
Error code C malfunction
Initial set-up value for a new detector
Normal working range
Slight contamination: Exchange detector
soon
Heavy contamination: Exchange detector
immediately
O fault: optical sensor is deactivated!
-20 °C ... +50 °C
-10 °C... +50 °C
Description
Low EMC level. No action required.
Medium EMC level. Consider location.
High EMC level. No suitable location.
Operation Guide
Maintenance and Service | en
2014.11 | 1.1 | F.01U.283.550