Setting The Indoor Unit Address - LG BECON HVAC BACnet PQNFB17C1 Installation & User Manual

Hide thumbs Also See for BECON HVAC BACnet PQNFB17C1:
Table of Contents

Advertisement

10
INSTALLING ACP BACnet

Setting the indoor unit address

By considering the entire installation configuration connecting to one ACP BACnet, set the address
to each indoor unit not to be overlapped. 00~FF in hexadecimal can be set to the indoor unit address.
However, in case of I/O module, address 00 should not be set because address 00 is used as
Broadcast in MODBUS communication.
Notes
Assigning indoor and outdoor unit number
If the outdoor unit product is Multi V, it is
recommended to assign the address by setting
the first digit of the address as the number of the
outdoor unit, and classifying the second digit as the
number or the indoor unit, for easy composition and
classification of the system.
Here is an example of configuring ACP BACnet and the device.
ACP BACnet
Power Distribution
Indicator (PDI)
Outdoor Units
PACP4B000
ERV
DI/DO, ON/OFF
Configuration
Address: 21
...
AHU
watt-hour meter
Indoor devices 1
Indoor devices 2
Configuration
Configuration
Address: 01
Address: 02
Configuration
Address: 11
Configuration
Address: 31
AWHP
Configuration
Address: 41
Indoor devices 3
Configuration
Address: 03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Becon hvac bacnet pqnfb17c0

Table of Contents