Compressor wire
Thermistor (Discharge)
Terminal Cover
Thermistor (Comp.temp.)
Remove the Thermistor(Comp.temp.)
and Thermistor(Discharge).
Remove the Terminal Cover and Compressor wire.
Remove the COMP BOLTs.
(3 places)
Discharge side
Heat up the brazed part of
the discharge side and disconnect.
Caution
There is a possibility of catching fire to oil when removing by the welding.
Procedure for compressor installation.
Reverse procedure to removing the compressor.
Precautions for installation of Compressor.
(1) When brazing, do not apply the flame to the terminal.
(2) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Cut the binder, and
remove the heat insulation.
HEATER (CRANK CASE)
Remove the BR Sheet before brazing.
And affix the BR Sheet after brazing.
Heat up the brazed part of the suction side and disconnect.
Remove the COMPRESSOR.
06-11
Remove the Thermistor(Discharge).
Loose the HEATER (CRANK CASE)
BR Sheet
Suction side
Hook