Status Menu - Pioneer PHR100-55 Instruction Manual

Pioneer water heater instruction manual
Table of Contents

Advertisement

1. Press
{S3}
once to access |C|, Heater Temperature Set Point. To adjust the temperature of the heater,
simply press in the
{S3}
(180). This number is the factory set point of 180
To change the temperature, push either
increases the set point temperature. The set point temperature can be set as low as 50
o
185
F. Changes are directly stored and the display returns to normal mode after one minute.
2. Press
{S3}
a second time. The heater will now display |Ch| and an alternating value of 15. This is the
Heater Differential Set Point. This function allows the installer to adjust the activation of the burner based
on the differential temperature setting of the heater. The burner will not start until the outlet water
temperature reaches a temperature equal to the setting for the heater, minus the differential.
EXAMPLE: The heater is set to heat at 180°F and the differential is set at 15°F. The burner will not start
until the outlet temperature of the system reaches 164°F (180° – 15° = 165°).
To adjust, press either
3. NOTE: Only in use if using an indirect storage tank. Press
Temperature Set Point |de| and an alternating value of 119. Range 95 – 180. To adjust, press either
(Decrease Value) or
{S2}
4. Press
{S3}
a fourth time to access |dh|, the Indirect Differential Set Point. This function allows the
installer to adjust the activation of the DHW call based on the differential temperature setting for the
indirect tank. The pump will not start until the indirect water temperature reaches a temperature equal to
the setting for the indirect, minus the indirect differential. Range 1 – 18. Default 7.
EXAMPLE: The indirect is set to heat at 130
start until the outlet temperature of the system reaches 119
5. Press
{S3}
a fifth time to access the final adjustment in this mode – |t|, the Temperature Measurement
in Fahrenheit to Celsius. To change value, press either
(Fahrenheit) to C (Celsius).
D. STATUS MENU
Installers are also able to check the current status of the heater parameters by pressing
seconds. Once activated, the display will show |d1| alternating value of the actual outlet temperature.
Actual values are displayed for each function. To view the next value, simply press the
Listed below are the values which can be displayed. These values cannot be changed. To exit this menu,
simply press
{S3}
to resume normal operation.
Function – Value
To toggle between values press
|d1| — Actual temperature from top sensor
|d2| — Actual temperature from bottom sensor
|d3| — Actual tank temperature if an indirect sensor is used.
|d4| — Not used
key for three seconds until you see a flashing (C) then an alternating value of
{S1}
or
(S1}
(Decrease Value) or
(Increase Value).
o
F and the differential is set to 10
{S1}
to go down and
o
F.
{S2}
on the display. The
{S2}
(Increase Value). Ranges 5° F to 30° F.
{S3}
a third time and you will see the Indirect
o
o
F (130
– 10
{S1}
or
{S2}
to change the measurement from F
{S4}
to go up. The first function you will see is:
{S1}
button decreases and
o
F or as high
o
F. The DHW pump will not
o
o
= 120
).
{S4}
for 3
{S4}
key.
51
{S2}
{S1}