When Connected To A Plc (Fx Series) Made By Mitsubishi Electric Corporation - Panasonic GT01 User Manual

Gt series programmable display
Hide thumbs Also See for GT01:
Table of Contents

Advertisement

5.3.4 When Connected to a PLC (FX Series) Made by Mitsubishi Electric
Corporation
For GT01, GT11 and GT21
Code No.
Time up error
ERFF
There is no response
from the PLC.
Data error
ER10
A data error occurred
during communication
Overrun error
ER12
The GT cannot receive
data.
PLC error
ER61
A NAK error has been
returned from the PLC.
For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Code No.
NAK error
ERFFFE
A NAK error has been
returned from the PLC.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Content
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
Check for errors in the communication conditions settings.
PLC runaway might be the problem.
Verify the PLC settings.
Content
Verify the PLC settings.
Cause and solution
Cause and solution