8. TEST OPERATION

CAUTION
Protection function will delay the startup of compressor for
3 minutes in case the unit is turned on immediately after power on or
restarted after shutdown.
The test operation must be carried out after the entire install has been
completed.
Please confirm the following points before the test operation:
The indoor unit and outdoor unit are installed properly.
Piping and wiring are correctly completed.
The refrigerant pipe system is leak-tested.
The drainage is unimpeded.
The heating insulation works correctly.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refrigerant
has been recorded.
The power voltage fits the rated voltage of the air conditioner.
There are no obstacles at the outlet and inlet of the outdoor and
indoor units.
The gas-side and liquid-side stop valves are both opened.
The air conditioner is pre-heated by turning on the power.
Mounted air conditioner indoor unit
According to the user's requirement, install the remote controller
holder where the remote controller's signal can reach the indoor unit
smoothly.
Test operation
Set the air conditioner under the mode of "COOLING" with the
remote controller, and check the following points per the "Owner's
Manual". If there is any malfunction, please resolve it through chapter
"Troubles And Causes".
The indoor unit
Ensure the switch on the remote controller works correctly.
Ensure the buttons on the remote controller works correctly.
Ensure the air flow louvre moves correctly.
Ensure the room temperature is adjusted well.
Ensure the indicator lights correctly.
Ensure the temporary buttons works well.
Ensure the drainage flows correctly.
Ensure no vibration or abnormal noise during operation.
Ensure the air conditioner heats well in the case of the HEATING/
COOLING type.
The outdoor unit
Ensure no vibration or abnormal noise during operation.
Whether the generated wind, noise, or condensed water produced by
the air conditioner has disturbed surrounding area.
Ensure none of the refrigerant has leaked.
TEST OPERATION | 11