5. Indoor Unit and Outside Unit Capacity Index
CAUTION
Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
A combination operation over 100% cause to reduce each indoor unit capacity.
 Combination ratio (50~200%)
Number of Outside units
Single Unit
Two Units combination
Three or more Units combination
Notes :
1. We can guarantee the operation only within 130% Combination Ratio.
If you want to connect more than 130% combination Ratio, please contact us and discuss the
requirement.
2. In case that operating indoor units ratio to rated capacity of Outside unit is more than 130%, the airflow
should be operated as low step in the all indoor units.
Heat Pump
General information
Combination Ratio
200 %
160 %
130 %