Page 4
Taiwan Class A compliance statement ....59 Avis de conformité à la réglementation Taiwan BSMI RoHS declaration ......60 d'Industrie Canada..........56 Australia and New Zealand Class A Index ............61 statement ............56 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Lenovo features or optional devices that are not addressed in this section. If you identify an unsafe condition, you must determine how serious the hazard is and whether you must correct the problem before you work on the product.
• Make sure that the insulation is not frayed or worn. 4. Remove the cover. 5. Check for any obvious non-Lenovo alterations. Use good judgment as to the safety of any non-Lenovo alterations. 6. Check inside the system for any obvious unsafe conditions, such as metal filings, contamination, water or other liquid, or signs of fire or smoke damage.
To avoid a shock hazard: • If Lenovo supplied a power cord(s), connect power to this unit only with the Lenovo-provided power cord. Do not use the Lenovo-provided power cord for any other product.
Page 9
Exchange only with the Lenovo-approved part. Recycle or discard the battery as instructed by local regulations. In the United States, Lenovo has a process for the collection of this battery. For information, call 1-800-426-4333. Have the Lenovo part number for the battery unit available when you call.
Page 10
• To avoid hazardous conditions due to uneven mechanical loading, always install the heaviest devices in the bottom of the rack cabinet. Always install servers and optional devices starting from the bottom of the rack cabinet. viii 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
In this case, a current transformer (CT) is used to detect the bypass current feedback voltage. If a current backfeed fault condition is detected, the UPS will terminate the inverter output to avoid personal injury. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Before installing your equipment, read the safety instructions. Then, follow the instructions in this manual for setting up and using the product. To discover the entire range of Lenovo products and the options available for the Lenovo UPS device, we invite you to visit our website or contact your Lenovo representative.
Page 14
End of life Lenovo will process products at the end of their service life in compliance with local regulations. Lenovo works with companies in charge of collecting and eliminating our products at the end of their service life. Product The product is made up of recyclable materials.
Page 15
• True online double-conversion technology with high power density, utility frequency independence, and power generator compatibility. • Advanced Battery Management (®ABM) technology that uses advanced battery management to increase battery service life, optimize recharge time, and provide a warning before the end of useful battery life. •...
Page 16
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
If you are shipping the UPS and its associated EBMs preinstalled in a rack, you must use the shipping bracket kit to prevent damage during shipment. The kit is available from Lenovo. Refer to the instructions in the kit to install the brackets properly. The brackets are not required when the UPS and EBMs are installed in a pre-positioned rack.
Primary group: 16A outlets for connection of critical equipment Group 1: (4) 10A programmable outlets for connection of equipment Group 2: (4) 10A programmable outlets for connection of equipment 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Input/Output terminal blocks Connectors for battery modules (to the UPS or to the other battery modules) Connectors for automatic recognition of battery modules Figure 3. 5594-6BX Accessories Part number Description 55946BX Extended Battery Module Control panel The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status, events, measurements and settings.
The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen. The following table describes the status information provided by the UPS. Note: If an other indicator appears, see Chapter 8 “Troubleshooting” on page 39 for additional information. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Operation status Cause Description Standby mode The UPS is Off. Equipment is not powered until power ) button is pressed. Online mode The UPS is operating normally. The UPS is powering and protecting the equipment. Battery mode A utility failure has occurred and the The UPS is powering the equipment UPS is on Battery mode.
Format: Date/time [US] [International] [US] Modify LCD screen brightness and contrast to be adapted to room light conditions. Audible alarm [Enabled] [Disabled on [Enabled] battery] [Always disabled] 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Page 23
Submenu Available settings Default settings Enable or disable the buzzer if an alarm occurs. In/Out settings Output voltage [200V] [208V] [220V] [230V] [208V] [240V] Can be changed only in Standby mode Output frequency Frequency converter: [Disabled] [Enabled] [Disabled] Frequency settable in frequency converter mode Output mode [Industrial] [Network]...
Page 24
If Enabled, LCD and communication stays ON 1h 30 min. after UPS is OFF. Remote command [Enabled] [Disabled] [Enabled] If Enabled, shutdown or restart commands from software are authorized. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Page 25
Submenu Available settings Default settings Bypass standby [Enabled] [Disabled] [Disabled] Define if output is powered from Bypass in Standby mode. Battery settings Automatic battery test In constant charge mode: [Every ABM cycle] [No test] [Every day] [Every week] [Every month] In ABM cycling mode: [No test] [Every ABM cycle] Low battery warning...
Page 26
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Note: Packing materials must be disposed of in compliance with all local regulations concerning waste. Recycling symbols are printed on Lenovo the packing materials to facilitate sorting. Checking the accessory kit Verify that the following additional items are included with the UPS:...
Battery power cable, attached with battery detection cable Stabilizer bracket (4 screws included) Rail kit for 19-inch enclosures Note: Disregard the EBM installation instructions if you are installing the EBM with a new UPS at the same time. Use the UPS instructions to install both the UPS and the EBM. If you ordered other UPS accessories, refer to specific user manuals to check the packing contents.
Step 3. Remove the two screws to pull out the metal protection cover of the battery pack. Note: A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Step 4. Pull out the plastic handle of the battery pack, and slide the packs out slowly on to a flat and stable surface. Use two hands to support the battery packs. Set them aside for reinstalling after that the UPS is rack mounted. Step 5.
Step 3. If installing additional units, place them next to the UPS in their final location. • Adjustment of the orientation of the LCD panel and of the logo. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
• Adjustment of the angle of vision of the LCD panel. Installing the communication card Follow these steps to install the UPS Network Management Card if it is not preinstalled. Note: It is not necessary to shut down the UPS before installing the card. Step 1.
Page 34
4-16 mm (12-6 6 mm (10 AWG) 10 lb in / 1.13 Nm AWG) 105°C Neutral N(L2) 10 mm (8 AWG) Ground 75°C Copper wire, solid or stranded. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Page 36
3. Insert the Output cable through the cable gland. 4. Connect the three cables to the Output terminal blocks. 5. Put back and secure the terminal blocks cover with the screw. 6. Tighten the cable glands. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Step 4. Set the upstream circuit breaker (not provided) to the "I" (on) position to switch on the utility power. The UPS front panel display illuminates and shows the Lenovo logo. Step 5. Verify that the UPS status screen shows , press to restart.
Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power. Monitoring the UPS operating mode The Lenovo UPS front panel indicates the UPS status through the UPS indicators. See “Control panel” on page 7. Operating modes: descriptions...
• the UPS has an overtemperature condition • the UPS has an overload condition listed in the Specifications section Note: The UPS stops operating after a specified delay for overload conditions listed in the Specifications section. However, the UPS remains on to alarm the fault. Standby mode When the UPS is turned off and remains connected to the AC source, the UPS is in Standby mode ( indicator).
The battery test might be cancelled due to bad conditions, or fail. Low battery warning During discharge, the low battery alarm is activated if the battery capacity goes below 20%. This threshold can be modified using the LCD panel. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
External battery setting The number of Extended Battery Modules (EBMs) is automatically detected, or it can be set manually using the LCD panel: see "External battery" in “User settings” on page 10. Deep discharge protection This setting is recommended to avoid damaging the battery packs. The warranty is void if deep discharge protection is disabled.
Page 42
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
RS232 or USB communication port on the UPS. The UPS can now communicate with Lenovo power management software. Relay output contacts The UPS incorporates four relay outputs; each one is available with a normally closed or open contact.
UPS by an external event, for example when the room temperature is too high. When RPO is activated, the UPS disables the output and all its power converters immediately. The UPS remains on, to alarm the fault. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Page 45
Important: The RPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits. Notes: Important notes: • The RPO must not be connected to any utility-connected circuits. The RPO switch must have a minimum rating of 27 Vdc and 20 mA and be a dedicated latching-type switch not tied into any other circuit.
If there is a utility power outage and the UPS battery power becomes low, the UPS Power Management suite can attempt to shut down your computer before the UPS shutdown occurs. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially trained persons, a lifting device, or both to safely lift this part or unit. (C011) 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
To replace the battery pack: Step 1. Remove the center section of the front bezel. Step 2. Loosen the two screws to open the left side of the front bezel. Step 3. Remove the two screws to pull out the metal protective cover of the battery pack. Note: A ribbon cable connects the LCD control panel to the UPS.
Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment. Refer to the Lenovo Systems Environmental Notices and User Guide on the Lenovo Documentation CD for more information. Important: •...
Chapter 8. Troubleshooting The Lenovo UPS is designed for durable, automatic operation. It will alert you whenever operating problems occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Page 52
UPS failure. UPS into Bypass mode. Check whether a remote operator has issued a command the UPS into Bypass mode. LED is on. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Page 53
Conditions Possible cause Action Power overload Power requirements exceed Remove some of the equipment from the UPS capacity (greater than 100% of UPS. nominal; see Appendix A “UPS model specifications” on page 45 for specific The UPS continues to operate, but it might output overload ranges).
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Note: For critical applications, immediate replacement might be available. Call your local service representative or the distributor nearest you. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Tier 1 CRU at your request without a service contract, you will be charged for the installation. • Tier 2 customer replaceable unit: You may install a Tier 2 CRU yourself or request Lenovo to install it, at no additional charge, under the type of warranty service that is designated for your compute node.
Page 56
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Appendix A. UPS model specifications The Lenovo 3U Rack or Tower UPS, model 5594-5KX and model 5594-6KX, is a single-phase UPS unit. Table 4. Power Module model list Model Power Ratings 5594-5KX 5000VA / 4500W at 200V, 208V, 220V, 230V, and 240V output...
Page 59
Table 11. AC input and output (continued) 5594-5KX 5594-6KX 230VAC, 5000VA, 4500W, 21.7A; 230VAC, 6000VA, 5400W, 26.1A; 240VAC, 5000VA, 4500W, 20.8A 240VAC, 6000VA, 5400W, 25.0A Table 12. Weights and dimensions (UPS) Model (UPS) Dimensions D x W x H (mm / inch) Weight (lb / kg) 5594-5KX 722 x 440 x 130 (28.4 x 17.3 x 5.1)
Page 60
Relay output contacts (4) relay outputs (normally open or normally closed) Remote On/Off 2 pins jumper (normally open) Remote Power Off 3 pins jumper (normally open or normally closed) 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Before you call, make sure that you have taken these steps to try to solve the problem yourself. If you believe that you require warranty service for your Lenovo product, the service technicians will be able to assist you more efficiently if you prepare before you call.
• Secure upload with the system serial number: https://www.ecurep.ibm.com/ app/upload_hw Creating a personalized support web page You can create a personalized support web page by identifying Lenovo products that are of interest to you. 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
IBM is Lenovo's preferred service provider for the System x, Flex System and NeXtScale System products. You can receive hardware service through your Lenovo reseller or from IBM. To locate a reseller authorized by Lenovo to provide warranty service, go to http://www.ibm.com/partnerworld and click Business Partner Locator.
Page 64
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...
Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead.
Lenovo encourages owners of information technology (IT) equipment to responsibly recycle their equipment when it is no longer needed. Lenovo offers a variety of prog rams and services to assist equipment owners in recycling their IT products. For information on recycling Lenovo products, go to:http://www.lenovo.com/recycling.
If Lenovo determines that the levels of particulates or gases in your environment have caused damage to the device, Lenovo may condition provision of repair or replacement of devices or parts on implementation of appropriate remedial measures to mitigate such environmental contamination.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Lenovo is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this e quipment. Unauthorized changes or modifications could void the user's authority to operate the equipment.
Verträglichkeit von Geräten), bzw. der EMV EU Richtlinie 2014/30/EU, für Geräte der Klasse A. Dieses Gerät ist berechtigt, in Übereinstimmung mit dem Deutschen EMVG das EG-Konformitätszeichen - CE - zu führen. Verantwortlich für die Konformitätserklärung nach Paragraf 5 des EMVG ist die Lenovo (Deutschland) GmbH, Meitnerstr. 9, D-70563 Stuttgart.
This is electromagnetic wave compatibility equipment for business (Type A). Sellers and users need to pay attention to it. This is for any areas other than home. Russia Electromagnetic Interference (EMI) Class A statement 3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide...