GE Multilin GEK-113328A Instruction Manual page 203

Generator protection & control system
Table of Contents

Advertisement

APPENDIX B
LOSS OF EXCITATION 1 > LOSS OF EXCITATION 2 > LOSS OF EXCITATION 3
SETTING DESCRIPTION
Function Permission
Center point in Ohms (sec) for Stage 1 Stage 1 Center
Radius value in Ohms (sec) for Stage
1
UV Supervision for stage 1
Trip time for Stage 1
Center point in Ohms (sec) for Stage 2 Stage 2 Center
Radius value in Ohms (sec) for Stage
2
UV Supervision for stage 2
Trip time for Stage 2
UV Supervision Level for both stages
1 and 2
Snapshot Event generation
GEK-113328A
NAME
DEFAULT VALUE
Function
DISABLED
10.00
Stage 1 Radius
8.00
Stage 1 UV Supv
DISABLED
Stage 1 Trip Delay
0.05
10.00
Stage 2 Radius
8.00
Stage 2 UV Supv
DISABLED
Stage 2 Trip Delay
0.05
UV Supv Level
40.0
Snapshot Events
ENABLED
G650 Generator Protection & Control System
B.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Ohm
[0.10 : 300.00]
0.01 Ohm
[0.10 : 300.00]
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 65.54]
0.01 Ohm
[0.10 : 300.00]
0.01 Ohm
[0.10 : 300.00]
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 65.54]
0.1 V
[0.0 : 500.0]
N/A
[DISABLED – ENABLED]
USER
VALUE
B
B-17